Appendix A: TV-VAVB3-E2 Points/Properties
TruVu™ VAVB3-E2 CARRIER CORPORATION ©2022
Installation and Start-up Guide All rights reserved
107
NOTE Engineering units shown in this document in the defaults and ranges are strictly for reference. You must
enter an integer only.
Status
Navigation:
i-Vu® / Field Assistant:
Properties > Control Program > Status
Point Name/Description
Range
Terminal Mode The controller's current operating status.
R:
Off
Heating
Warm-up
Vent
Cooling
Dehumidify
Reheat
Pressurize
Evacuate
Shutdown
IAQ Override
Air Balancing
Terminal Type The type of zone terminal that the controller is installed on.
R:
Single Duct
Parallel Fan
Series Fan
Space Temperature - Prime Variable The space temperature value currently used for
control.
R:
-56 to 245°F
(-48.9 to 118.3°C)
Primary Airflow The current airflow measured through the primary air damper.
R:
0 to 99999 cfm
(liters/second)
Damper Position The current damper position.
R:
0 to 100%
Supply Air Temperature Displays the current supply air temperature.
R:
-56 to 245°F
(-48.9 to 118.3°C)
Heating Capacity The current reheat capacity when the zone is configured for reheat.
R:
0 to 100%
Baseboard Heating Capacity The current baseboard heat capacity when the zone is
configured for Combination Baseboard or Non-ducted Heat.
R:
0 to 100%
Outdoor Air Temperature The current outdoor air temperature from a linked air
source, if available, or from another network source.
R:
-56 to 245°F
(-48.9 to 118.3°C)