Appendix A: TV-VAVB3-E2 Points/Properties
TruVu™ VAVB3-E2 CARRIER CORPORATION ©2022
Installation and Start-up Guide All rights reserved
107
NOTE Engineering units shown in this document in the defaults and ranges are strictly for reference. You must
enter an integer only.
Status
Properties > Control Program > Status
Terminal Mode – The controller's current operating status.
Off
Heating
Warm-up
Vent
Cooling
Dehumidify
Reheat
Pressurize
Evacuate
Shutdown
IAQ Override
Air Balancing
Terminal Type – The type of zone terminal that the controller is installed on.
Single Duct
Parallel Fan
Series Fan
Space Temperature - Prime Variable – The space temperature value currently used for
control.
-56 to 245°F
(-48.9 to 118.3°C)
Primary Airflow – The current airflow measured through the primary air damper.
0 to 99999 cfm
(liters/second)
Damper Position – The current damper position.
Supply Air Temperature – Displays the current supply air temperature.
-56 to 245°F
(-48.9 to 118.3°C)
Heating Capacity – The current reheat capacity when the zone is configured for reheat.
Baseboard Heating Capacity – The current baseboard heat capacity when the zone is
configured for Combination Baseboard or Non-ducted Heat.
Outdoor Air Temperature – The current outdoor air temperature from a linked air
source, if available, or from another network source.
-56 to 245°F
(-48.9 to 118.3°C)
Appendix A: TV-VAVB3-E2 Points/Properties