EasyManua.ls Logo

Carrier TruVu VAVB3-E2 - To Wire the Relative Humidity Sensor to the Controller

Carrier TruVu VAVB3-E2
155 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Wiring sensors to the TV-VAVB3-E2's inputs
TruVu™ VAVB3-E2 CARRIER CORPORATION ©2022
Installation and Start-up Guide All rights reserved
38
To wire the Relative Humidity sensor to the controller
Part #33ZCSENSRH-02
The Relative Humidity (RH) sensor is used for zone humidity control (dehumidification) if the rooftop unit has a
dehumidification device. If not, the sensor only monitors humidity.
NOTE Do not use a relative humidity sensor and CO
2
sensor on the same zone controller.
1 Strip the outer jacket from the cable for at least 4 inches (10.2 cm). Strip .25 inch (.6 cm) of insulation from
each wire.
2 Wire the sensor to the controller. See diagram below.
3 Using electrical tape, insulate any exposed resistor lead to prevent shorting.
4 Set SW3 on the sensor as shown below.

Table of Contents

Related product manuals