Adjusting the TV-VAVB3-E2 driver properties
TruVu™ VAVB3-E2 CARRIER CORPORATION ©2022
Installation and Start-up Guide All rights reserved
77
Device
The Device page provides the following information plus the items described in the table below:
• BACnet device object properties for the TV-VAVB3-E2
• The character sets supported by this device for BACnet communication
• The controller clock's time and date
The current state of the controller:
Operational
Download in Progress
Download Required
Backup in Progress
Non-Operational
The following fields refer to all networks over which the TV-VAVB3-E2 communicates.
How many milliseconds the device will wait before resending a message if no
response is received.
How many milliseconds the device will wait before resending a message segment
if no response is received.
The number of times the device will resend a message.
Notification Classes
A BACnet alarm's Notification Class defines:
• Alarm priority for Alarm, Fault, and Return to Normal states
• Options for BACnet alarm acknowledgment
• Where alarms should be sent (recipients)
Alarms in the i-Vu® application use Notification Class #1. The i-Vu® application is automatically a recipient of
these alarms.
NOTE BACnet defines the following Network message priorities for Alarms and
Events.
BACnet priority for Alarms.
BACnet priority for Fault messages.
BACnet priority for Return-to-normal messages.