Adjusting the TV-VAVB3-E2 driver properties
TruVu™ VAVB3-E2 CARRIER CORPORATION ©2022
Installation and Start-up Guide All rights reserved
80
Custom Translation Tables
You can set up a translation table that an analog input will use to translate the raw data from a non-linear sensor
to the engineering units you want it to provide on the output wire of the Analog Input microblock. In the navigation
tree, select Custom Translation Table #1, #2, or #3. The Properties page has instructions.
For the input to use the translation table, go to the control program's Properties page > I/O Points tab. Click the
analog input in the Name column. On the Details tab, set Sensor Type (Scaling Method) to Non-Linear, Custom
Table #__.
BACnet Controller Properties
The BACnet Controller Properties page provides the following information plus the items described in the table
below:
• The TV-VAVB3-E2's Ethernet MAC address
• Whether Port S1 is being used for MS/TP and is disabled
NOTE The options shown on the page change according to your controller's settings.
To increase MS/TP performance, enter the highest address used on the MS/TP
network for a master controller. This number must be less than or equal to 127.
This is the maximum number of information messages a controller may transmit
before it must pass the token to the next controller. Valid values are 1 to 255.
TIP Set Max Info Frames to a number in the range 20 to 100 so that the
router does not become a bottleneck for traffic being routed from a high-speed
network to the slower MS/TP network.
When this field is enabled, you can set up IP addressing through a tool. IP
addressing is typically set up through the Service Port.