Appendix A: TV-VAVB3-E2 Points/Properties
TruVu™ VAVB3-E2 CARRIER CORPORATION ©2022
Installation and Start-up Guide All rights reserved
130
Point Name/Description
Default/Range
Occupancy
BAS On/Off Determines the occupancy state of the controller and can be set over the
network by another device or third party BAS.
Options:
Inactive Occupancy is determined by a configured schedule.
Occupied The controller is always in the occupied mode.
Unoccupied The controller is always in the unoccupied mode.
NOTE If BAS On/Off is set to either Unoccupied or Occupied, the Optimal Start routine
is automatically disabled.
D:
R:
Inactive
Inactive
Occupied
Unoccupied
Schedules The controller's occupancy status based on the local schedule.
R:
Unoccupied/Occupied
Pushbutton Override Active indicates if a user pushed the sensor's override button to
override the occupancy state.
R:
Off/Active
Override Time Remaining The amount of time remaining in an override period.
R:
0 to 480 minutes
Occupancy Contact Status The physical state of the controller's IN-04 input.
R:
Inactive
Inactive
Active Unoccupied/Stdby
Global Occupancy The System Occupancy network input's current state.
D:
R:
Unoccupied
Unoccupied/Occupied
Local BACnet Schedule
R:
Off/On
Configure ZS Sensors by setting the following options in the Local BACnet Schedule
microblock popup. Click Local BACnet Schedule to access the microblock popup
Properties page > Details tab.
See the microblock Help for more detailed explanations.
Sensor Configuration
Allow Force Unoccupied: Check to allow a user to save energy by
forcing the zone into an unoccupied schedule on the ZS sensor. The
user does this by holding the sensor's On/Off button for at least 3
seconds. This forced state remains in effect until the schedule
transitions to unoccupied or until a user presses the sensor's On/Off
button again.
D:
R:
Enabled
Disabled/Enabled
Force Unoccupied without Delay: Check to allow a user to force a zone
to unoccupied immediately instead of the normal 3-second delay.
NOTE This option is not available if Allow TLO Set During Occupied is
checked.
D:
R:
Enabled
Disabled/Enabled
Timed Local Override
Increment: Minutes that the microblock adds to the zone's occupied
time for each click of the zone's local override button or switch.
D:
30:00 mm:ss
Maximum Duration: Maximum value (up to 960 minutes) the
microblock outputs, regardless of additional pulses from the controller's
input.
D:
R:
60:00 mm:ss
0 to 960:00 mm:ss