Appendix A: TV-VAVB3-E2 Points/Properties
TruVu™ VAVB3-E2 CARRIER CORPORATION ©2022
Installation and Start-up Guide All rights reserved
138
Occupancy Contact State - Current hardware state of the controller's IN-04 input.
R:
Open/Closed
Sensor Invalid This internal input monitors the communication between the controller
and the SPT sensor. Off indicates communication is normal.
R:
Off/On
Rnet Sensed Occupancy Displays occupancy status detected by wireless infrared
motion sensor.
R:
Off/On
Hot Water Valve - The current value of the controller's AO-01 output.
R:
0 to 100%
Hot Wtr Vlv 1 The current value of the controller's output to the Smart Valve.
R:
0 to 100%
Heating Stage 1 - The current hardware state of the controller's BO-01 output.
R:
Off/On
Heating Stage 2 - The current hardware state of the controller's BO-02 output.
R:
Off/On
Fan S/S or EH 3 - The current hardware state of the controller’s BO-03 output. The
function of this output depends on the terminal type.
R:
Off/On