EasyManuals Logo

CleaverBrooks ProtoNode User Manual

CleaverBrooks ProtoNode
136 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #89 background imageLoading...
Page #89 background image
ProtoNode Gateway
750-426 87
Surge Tank Lvl Lo BI 99 DI 99 11449 nvoSgTkLvlLo_XXX SNVT_switch
Surge Tank Temp BAD QUALITY BI 100 DI 100 11450 nvoSgTkTmpBQ_XXX SNVT_switch
Surge Tank Temp Lo BI 101 DI 101 11451 nvoSgTkTmpLo_XXX SNVT_switch
Surge Tank Temp Hi BI 102 DI 102 11452 nvoSgTkTmpHi_XXX SNVT_switch
Transfer Pump 1 Flt BI 103 DI 103 11453 nvoXfrPm1Flt_XXX SNVT_switch
Transfer Pump 2 Flt BI 104 DI 104 11454 nvoXfrPm2Flt_XXX SNVT_switch
Transfer Pump 3 Flt BI 105 DI 105 11455 nvoXfrPm3Flt_XXX SNVT_switch
Transfer Pump 1 OVERLOAD BI 106 DI 106 11456 nvoXfrP1OvLd_XXX SNVT_switch
Transfer Pump 2OVERLOAD BI 107 DI 107 11457 nvoXfrP2OvLd_XXX SNVT_switch
Transfer Pump 3OVERLOAD BI 108 DI 108 11458 nvoXfrP3OvLd_XXX SNVT_switch
Surge Tank Lo-Lo (LWCO) BI 109 DI 109 11459 nvoSgTkLWCO_XXX SNVT_switch
Surge Tank Header Pressure Hi BI 110 DI 110 11460 nvoSgTkHdPHi_XXX SNVT_switch
Surge Tank Header Pressure Lo BI 111 DI 111 11461 nvoSgTkHdPLo_XXX SNVT_switch
Surge Tank Header Pressure BAD QUALITY BI 112 DI 112 11462 nvoSgTkHPrBQ_XXX SNVT_switch
DAB1[7]0 BI 113 DI 113 11463 nvoDAB1_7_0_XXX SNVT_switch
DAB1[7]1 BI 114 DI 114 11464 nvoDAB1_7_1_XXX SNVT_switch
DAB1[7]2 BI 115 DI 115 11465 nvoDAB1_7_2_XXX SNVT_switch
Surge 2nd Feed Wtr Valve Open BI 116 DI 116 11466 nvoSg2FdWVlO_XXX SNVT_switch
Transfer Pump 1 FLo Flt BI 117 DI 117 11467 nvoXfr1FloFl_XXX SNVT_switch
Transfer Pump 2 FLo Flt BI 118 DI 118 11468 nvoXfr2FloFl_XXX SNVT_switch
Transfer Pump 3 FLo Flt BI 119 DI 119 11469 nvoXfr3FloFl_XXX SNVT_switch
Transfer Pump 1 VSD Speed Feedback BQ BI 120 DI 120 11470 nvoXfr1VSDBQ_XXX SNVT_switch
Transfer Pump 2 VSD Speed Feedback BQ BI 121 DI 121 11471 nvoXfr2VSDBQ_XXX SNVT_switch
Transfer Pump 3 VSD Speed Feedback BQ BI 122 DI 122 11472 nvoXfr3VSDBQ_XXX SNVT_switch
DAB1[7]10 BI 123 DI 123 11473 nvoDAB1_7_10_XXX SNVT_switch
DAB1[7]11 BI 124 DI 124 11474 nvoDAB1_7_11_XXX SNVT_switch
DAB1[7]12 BI 125 DI 125 11475 nvoDAB1_7_12_XXX SNVT_switch
DAB1[7]13 BI 126 DI 126 11476 nvoDAB1_7_13_XXX SNVT_switch
DAB1[7]14 BI 127 DI 127 11477 nvoDAB1_7_14_XXX SNVT_switch
DAB1[7]15 BI 128 DI 128 11478 nvoDAB1_7_15_XXX SNVT_switch
Surge Tank No Alarms Relay OK BI 129 DI 129 11479 nvoSTNoAlRel_XXX SNVT_switch
YelLo Stack Light ON BI 130 DI 130 11480 nvoSTYlStkLt_XXX SNVT_switch
Green Stack Light ON BI 131 DI 131 11481 nvoSTGrStkLt_XXX SNVT_switch
RED Stack Light ON BI 132 DI 132 11482 nvoSTRdStkLt_XXX SNVT_switch
Surge Tank Feed Wtr Valve Open BI 133 DI 133 11483 nvoSTFdWtVlO_XXX SNVT_switch
ST Lo Lo Wtr Cutoff Relay Energized BI 134 DI 134 11484 nvoSTCtoRlEn_XXX SNVT_switch
Transfer Pump 1 ON BI 135 DI 135 11485 nvoXfrPm1ON_XXX SNVT_switch
Transfer Pump 2 ON BI 136 DI 136 11486 nvoXfrPm2ON_XXX SNVT_switch
Transfer Pump 3 ON BI 137 DI 137 11487 nvoXfrPm3ON_XXX SNVT_switch
Transfer Pump 1 In AUTO BI 138 DI 138 11488 nvoXfP1InAut_XXX SNVT_switch
Transfer Pump 2 In AUTO BI 139 DI 139 11489 nvoXfP2InAut_XXX SNVT_switch
Transfer Pump 3 In AUTO BI 140 DI 140 11490 nvoXfP3InAut_XXX SNVT_switch
Transfer Pumps ALT MODE ON BI 141 DI 141 11491 nvoXfPAlMdOn_XXX SNVT_switch
DAB1[8]13 BI 142 DI 142 11492 nvoDAB1_8_13_XXX SNVT_switch
DAB1[8]14 BI 143 DI 143 11493 nvoDAB1_8_14_XXX SNVT_switch
DAB1[8]15 BI 144 DI 144 11494 nvoDAB1_8_15_XXX SNVT_switch
DAB1[9]0 BI 145 DI 145 11495 nvoDAB1_9_0_XXX SNVT_switch
DAB1[9]1 BI 146 DI 146 11496 nvoDAB1_9_1_XXX SNVT_switch
DAB1[9]2 BI 147 DI 147 11497 nvoDAB1_9_2_XXX SNVT_switch
DAB1[9]3 BI 148 DI 148 11498 nvoDAB1_9_3_XXX SNVT_switch
ADAC Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued)
RER LER
Point Name
BACnet
Data
Type
BACnet
Object Id
N2
Data
Type
N2 Point
Address
Modbus
Register
Lon Name Lon SNVT Type

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CleaverBrooks ProtoNode and is the answer not in the manual?

CleaverBrooks ProtoNode Specifications

General IconGeneral
BrandCleaverBrooks
ModelProtoNode
CategoryGateway
LanguageEnglish