ProtoNode Gateway
92 750-426
External Device Start BI 50 DI 50 10050 nvoExtDevSt_XXX SNVT_switch
Non Recycle Limit Relay BI 51 DI 51 10051 nvoNoRecLmRl_XXX SNVT_switch
Drive to Low Fire (FARC) BI 52 DI 52 10052 nvoDrv2LoFir_XXX SNVT_switch
Start Slave Blr (2 Blr LL) BI 53 DI 53 10053 nvoStrtSlvBl_XXX SNVT_switch
Load Demand Output BI 54 DI 54 10054 nvoLdDemOut_XXX SNVT_switch
Alarm Output BI 55 DI 55 10055 nvoAlmOut_XXX SNVT_switch
Boiler Ready (LL) BI 56 DI 56 10056 nvoBlrRdyLL_XXX SNVT_switch
Boiler Load Demand BI 57 DI 57 10057 nvoBlrLdDem_XXX SNVT_switch
Firing Rate Remote/Llag BI 58 DI 58 10058 nvoFrRatRmLL_XXX SNVT_switch
Firing Rate Manual BI 59 DI 59 10059 nvoFirRatMan_XXX SNVT_switch
Firing Rate Auto BI 60 DI 60 10060 nvoFrRatAuto_XXX SNVT_switch
Hot Stand By BI 61 DI 61 10061 nvoHotStndBy_XXX SNVT_switch
Warm Up BI 62 DI 62 10062 nvoWarmUp_XXX SNVT_switch
Fuel 3 Selected BI 63 DI 63 10063 nvoFl3Sel_XXX SNVT_switch
Aux Alarm 3 BI 64 DI 64 10064 nvoAuxAlm3_XXX SNVT_switch
Steam or Hot Water BI 65 DI 65 10065 nvoStmHotWtr_XXX SNVT_switch
Level Master Present BI 66 DI 66 10066 nvoLvlMstPrs_XXX SNVT_switch
Variable Speed Drive Present BI 67 DI 67 10067 nvoVarSpDrPr_XXX SNVT_switch
Economizer Present BI 68 DI 68 10068 nvoEcPrs_XXX SNVT_switch
Combustion Air Temp Present BI 69 DI 69 10069 nvoCmArTpPrs_XXX SNVT_switch
Oil Temp Sensor Present BI 70 DI 70 10070 nvoOlTpSenPr_XXX SNVT_switch
O2 Analyzer Present BI 71 DI 71 10071 nvoO2AnlzrPr_XXX SNVT_switch
Feedwater or Return Temp Present BI 72 DI 72 10072 nvoFdWRtTpPr_XXX SNVT_switch
Outdoor Reset Selected BI 73 DI 73 10073 nvoOutResSel_XXX SNVT_switch
Parallel Positioning Selected BI 74 DI 74 10074 nvoParPsngSl_XXX SNVT_switch
Two boiler lead lag master select BI 75 DI 75 10075 nvo2BLLMstSl_XXX SNVT_switch
Two boiler lead lag slave select BI 76 DI 76 10076 nvo2BLLSlvSl_XXX SNVT_switch
Master panel select BI 77 DI 77 10077 nvoMstPnlSel_XXX SNVT_switch
Hot stand by select BI 78 DI 78 10078 nvoHotStbySl_XXX SNVT_switch
Dual setpoint select BI 79 DI 79 10079 nvoDualSPSel_XXX SNVT_switch
Gas Flow Select BI 80 DI 80 10080 nvoGsFloSel_XXX SNVT_switch
Oil Flow Select BI 81 DI 81 10081 nvoOilFloSel_XXX SNVT_switch
Steam Flow Select BI 82 DI 82 10082 nvoStmFloSel_XXX SNVT_switch
Water Flow Select BI 83 DI 83 10083 nvoWtrFloSel_XXX SNVT_switch
Honeywell or Fireye BI 84 DI 84 10084 nvoHnywlFrey_XXX SNVT_switch
High Water Alarm BI 85 DI 85 10085 nvoHiWtrAlm_XXX SNVT_switch
Oil Drive out of Position Alarm BI 86 DI 86 10086 nvoOlDrvPsAl_XXX SNVT_switch
FGR Drive out of Position Alarm BI 87 DI 87 10087 nvoFGRDrPsAl_XXX SNVT_switch
Air Actuator FB Alarm Low BI 88 DI 88 10088 nvoArAcFBALo_XXX SNVT_switch
Air Actuator FB Alarm High BI 89 DI 89 10089 nvoArAcFBAHi_XXX SNVT_switch
Fuel1 Actuator FB Alarm Low BI 90 DI 90 10090 nvoFl1AcFBLo_XXX SNVT_switch
Fuel1 Actuator FB Alarm High BI 91 DI 91 10091 nvoFl1AcFBHi_XXX SNVT_switch
Fuel2 Actuator FB Alarm Low BI 92 DI 92 10092 nvoFl2AcFBLo_XXX SNVT_switch
Fuel2 Actuator FB Alarm High BI 93 DI 93 10093 nvoFl2AcFBHi_XXX SNVT_switch
FGR Actuator FB Alarm Low BI 94 DI 94 10094 nvoFGRAcFBLo_XXX SNVT_switch
FGR Actuator FB Alarm High BI 95 DI 95 10095 nvoFGRAcFBHi_XXX SNVT_switch
VSD Deviation Alarm BI 96 DI 96 10096 nvoVSDDevAlm_XXX SNVT_switch
Flame Strength Honeywell AI 1 AI 1 30001 nvoFlmStrHny_XXX SNVT_count_f
Combustion Air Fan Speed AI 2 AI 2 30003 nvoCmArFnSpd_XXX SNVT_count_f
Blower Motor Kw AI 3 AI 3 30005 nvoBlwMtrKw_XXX SNVT_count_f
Hawk ICS Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus and LonWorks (Continued)
RER RER
Point Name
BACnet
Data Type
BACnet
Object Id
N2
Data
Type
N2 Point
Address
Modbus
Register
Lon Name Lon SNVT Type