STANDING PILOT CONTROL TROUBLESHOOTING GUIDE
c:,
z
-
z
a:
<
3:
I
I
I
I
I
I
I
I
I
I
START
LIGHT PILOT BURNER
(PILOT BURNER STAYS LIT)
YES
,.
SET THERMOSTAT
TO CALL FOR HEAT
YES
,
INDUCED DRAFT MOTOR STARTS
YES
'
MAINBURNER LIGHTS
YES
,~
INDOOR BLOWER MOTOR
STARTS AFTER 20 SECONDS
YES
w
SYSTEM RUNS UNTIL
CALL FOR HEAT ENDS
YES
'
TURN THERMOSTAT TO OFF-
VALVE SHUTS FLAME OFF
YES
1W
INDUCED DRAFT MOTOR STOPS
YES
INDOOR BLOWER MOTOR STOPS
AFTER 90/120/150/180 SECONDS
YES
TROUBLESHOOTINGENDS
I NO
I
I
NO
I NO
I
INO
I
I NO
I
I NO
I
I NO
l
I
-
-
-
CHECK INLET GAS PRESSURE
-
CHECK PILOT FLAME AROUND THERMOCOUPLE
CHECK THERMOCOUPLE FITTING AT GAS VALVE
yYES
REPLACE THERMOCOUPLE
NO
- REPUICE GAS VALVE
-
CHECK LINE VOLTAGE TO CONTROL BOARD
CHECK LOW VOLTAGE TRANSFORMER
CHECK LOW VOLTAGE TRANSFORMER FUSE
CHECK LIMITS (CLOSED)
CHECK WIRING
CHECK
FANFOR 115VAC TO !OMMOTOR
NO
- REPLACE
-
CONTROL
f YES
BOARD
REPLACE
IDMMOTOR
I
REPLACE
CHECK FOR BLOCKED VENT
NO
PRESSURE
CHECK NEGATIVE PRESSURE CONTROL
CONTROL
!CLOSED)
CHECK24 VOLTS TOGAS VALVE
NO
REPLACE
-
CHECK FOR GAS FLOW TO AND FROM VALVE
CONTROL
I
BOAADIF
f NO
WIRING IS OK
REPLACEVALVE
I
CHECK FOR 115VAC ACROSS BLOWER
INO
MOTOR TERMINALS ON CONTROL BOARD
REPLACE
-
-
CHECK CAPACITOR
CONTROL
I
BOARD IF
yNO
WIRINGTO
MOTOR IS OK
REPLACE BLOWER MOTOR
I
.
CHECK FOR PROPER THERMOSTAT OPERATION
-
REMOVEVALVELEADATGASVALVE
-
IF VALVE CLOSES. RECHECK THERMOSTAT AND WIRING.
-
-
-
IF VALVE DOES NOT CLOSE, REPLACE VALVE,
REPLACE CONTROL BOARD
I
CHECK FOR OPEN LIMIT: I
REPLACECONTROL BOARD
REPEAT PROCEDURE UNTIL
TROUBLE-FREE OPERATION IS OBTAINED.
59