RESTORE POWER TO UNIT
• IF CHECKS ARE OK, REPLACE IFC
-
• CHECK FOR 115 VAC ACROSS BLOWER
MOTOR AND BLOWER MOTOR TERMINALS
~REPLACE IFC IF
NO WIRING TO BLOWER
(HEAT AND NEUTRAL) ON IFC MOTOR IS OK
.YES
REPLACE BLOWER MOTOR
I
SYSTEM RUNS
NO
I NOTE: IF IFC GOES INTO LOCKOUT WAIT 30 SECONDS THEN
UNTIL CALL FOR
-
RESET SYSTEM
HEAT ENDS
I I
• CHECK CONTINUITY OF GROUND WIRE. NOTE: IF GROUND IS
YES
POOR OR ERRATIC, SHUTDOWN MAY OCCUR OCCASIONALLY EVEN
THOUGH OPERATION IS NORMAL AT THE TIME OF CHECKOUT.
• CHECK FLAME SENSE CURRENT
• CHECK FOR EXCESSIVE HEAT AT IGNITER BASE, (TEMP.
ABOVE 1000 F (538 C) CAUSES SHORT TO GROUND)
• TURN POWER OFF TO UNIT.
• CLEAN FLAME SENSOR WITH STEEL WOOL.
• RESTORE POWER TO UNIT.
'
• IF CHECKS ARE OK, REPLACE IFC
TURN THERMOSTAT TO OFF
• CHECK FOR PROPER THERMOSTAT OPERATION.
I
-
VALVE SHUTS OFF
REMOVE VALVE LEAD AT IFC
FLAME GOES OUT
I I
NO
IF VALVE CLOSED, RECHECK THERMOSTAT AND
YES
WIRING. IF NOT, REPLACE VALVE.
• CHECK FOR OPEN LIMIT. ,
I
DRAFT MOTOR STOPS AFTER 5 SEC.
NO
-
REPLACEIFC
tYES
GAS VALVE OPENS AND
I
MAIN BURNER LIGHTS
YES
.
I
MAIN BURNER
REMAINS POWERED
AND LIT
I
NO
I
I
NO
I
YES
INDOOR BLOWER MOTOR
I
NO
ST ARTS 20 SECONDS
AFTER MAIN GAS VALVE OPENS
I I
INDOOR BLOWER MOTOR
STOPS AFTER
I
90/120/160/180 SECONDS
YES
I
TROUBLESHOOTING ENDS
I
NOTE:
REPLACE IGNITERl
SYSTEM WILL ATTEMPT TO LIGHT 4 TIMES.
VOLTAGE IS PRESENT AT THE VALVE FOR
ONLY 8 SECONDS DURING EACH TRIAL FOR
IGNITION (SYSTEM WILL GO INTO A 1-HOUR
LOCKOUT AFTER 4 TRIES). THE BLOWER AND
ICM WILL RUN 180 SEC. IF THE SECOND
IGNITION TRIAL FAILS TO SENSE FLAME.
• CHECK FOR 24 VAC ACROSS THE VALVE
AND VALVE TERMINALS ON THE IFC
f YES
• CHECK IGNITER POSITION.
I
• CHECK FOR GAS FLOW TO AND FROM VALVE.
f NO
REPLACE VALVE IF NO
I
FLOW THAU VALVE
NOTE: IF IFC GOES INTO LOCKOUT WAIT 30 SECONDS THEN
-
RESET SYSTEM
-
• CHECK POLARITY OF 115 VAC SUPPLY
• CHECK CONTINUITY OF GROUND WIRE
CHECK INSULATION ON IGNITER LEADS
CHECK FLAME SENSE CURRENT (YELLOW LED)
LED IS ON IF FLAME CURRENT IS GOOD,
IT FLASHES IF CURRENT IS MARGINAL.
TURN POWER OFF TO UNIT
• CLEAN FLAME SENSOR WITH STEEL WOOL IF LED FLASHES
I
NO
-
-
• CHECK FOR OPEN LIMIT. ,
REPLACE IFC
I
REPEAT PROCEDURE UNTIL TROUBLEFREE
OPERATION IS OBTAINED.
STATIC DISCHARGE CAN DAMAGE INTEGRATED FURNACE CONTROL (IFC)
* "OK" LED BLINKS TO INDICATE EXTERNAL FAULTS:
(1) BLINK FOLLOWED BY A 2 SEC. PAUSE-1 HOUR LOCKOUT
(2) BLINKS FOLLOWED BY A 2 SEC. PAUSE - PRESSURE SWITCH IS OPEN
(3) BLINKS FOLLOWED BY A 2 SEC. PAUSE - LIMIT SWITCH IS OPEN
(4) BLINKS FOLLOWED BY A 2 SEC. PAUSE - PRESSURE SWITCH CLOSED
92-22744-10-03