Byte
Bit
Name/Signal
Description
Reference
4
SSR Active
Safe Speed Range activated
6.3.4.4 The SSR Signals
5
SLS 1 Active
Safe Limited Speed Limit1 activated
6.3.2.5 The SLS Signals
6
SLS 2 Active
Safe Limited Speed Limit2 activated
6.3.2.5 The SLS Signals
7
SLS 3 Active
Safe Limited Speed Limit3 activated
6.3.2.5 The SLS Signals
3
0
1
2
SSM Active
Safe Speed Monitor activated
6.3.5.4 The SSM Signals
3
SMS Active
Safe Maximum Speed activated
6.3.3.3 The SMS Signals
4
5...7
4
0
SSM_Above_Max_Limit
6.3.5.4 The SSM Signals
1
SSM_Below_Min_Limit
6.3.5.4 The SSM Signals
2
SF_Activity
Shows if any safety function is ac-
tive
(1)
3...6
7
Advanced safety optionboard in
error state
5
0
DIN1
Safe Digital Input 1 state
3.4 Determining the Achieved Safety
Level
1
DIN2
Safe Digital Input 2 state
3.4 Determining the Achieved Safety
Level
2
DIN3
Safe Digital Input 3 state
3.4 Determining the Achieved Safety
Level
3
DIN4
Safe Digital Input 4 state
3.4 Determining the Achieved Safety
Level
4
DOUT1
Safe Digital Output 1 state
3.4 Determining the Achieved Safety
Level
5
DOUT2
Safe Digital Output 2 state
3.4 Determining the Achieved Safety
Level
6..7
1
When the SSM function is parameterized to "Always active", it is not included in this bit.
AQ319736045637en-000101 / DPD01798124 | Danfoss A/S © 2021.06
Safe Fieldbuses
VACON® NXP Advanced Safety Options
Operating Guide

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VACON OPTEA and is the answer not in the manual?

Danfoss VACON OPTEA Specifications

General IconGeneral
BrandDanfoss
ModelVACON OPTEA
CategoryDC Drives
LanguageEnglish

Related product manuals