8 Parameter List
8.1 General Parameters
8.1.1 Parameter File Parameters
Table 63: Parameter File Parameters
Parameter
Selection
Unit
Description
File Name
A maximum of 32 ASCII char-
acters.
Use this parameter to give a name for this parameter file. The first 12 char-
acters are visible on the control panel of the drive.
File Creator
A maximum of 32 ASCII char-
acters.
Use this parameter to write the name of the person who created the param-
eter file. The first 12 characters are visible on the control panel of the drive.
File Date
Use this parameter to select the creation date of the parameter file.
Company
A maximum of 32 ASCII char-
acters.
Use this parameter to write the name of the employer of the file creator.
Comment
A maximum of 120 ASCII
characters.
Use this parameter to write a description of the parameter file.
8.1.2 Common Safety Function Parameters
Table 64: Common Safety Function Parameters
Parameter
Selection
Unit
Description
Zero Speed
1...999
rpm
Use this parameter to set the speed at which the motor is considered to be stopped. The safe
stopping functions become reached at this speed. Zero Speed is also used in other situa-
tions. For example, the SS2 function activates the SOS function after the speed has reached
Zero Speed and the time set with SS2 td2 has passed.
Drive Ac-
knowledg-
ment
Enabled
Disabled
Use this parameter to select whether the control board of the drive is permitted to acknowl-
edge safety functions in the Advanced safety option board. The source of the acknowledg-
ment can be, for example, the control panel of the drive or a non-safe fieldbus.
Drive Reset
Enabled
Disabled
Use this parameter to select whether the control board of the drive is permitted to reset
faults in the Advanced safety option board. The source of the reset can be, for example, the
control panel of the drive or a non-safe fieldbus.
Acknowl-
edgment
Mode (Start-
up)
Manual
Automatic
Use this parameter to select whether a manual (external) acknowledgment is necessary to
deactivate the STO function after the start-up of the AC drive. If you select automatic, the
STO function is deactivated after a successful start-up.
8.1.3 Speed Measurement Parameters
Table 65: Speed Measurement Parameters
Parameter
Selection
Unit
Description
Encoder Type
No encoder
Sin/Cos
Two Proximity sensors
HTL and proximity sensor
TTL and proximity sensor
HTL and estimated speed
TTL and estimated speed
Sin/Cos and proximity sensor
Use this parameter to select the encoder type. With a Sin/Cos or a
TTL encoder, it is necessary to define whether termination is used
on the encoder interface board. See 3.6.4 Encoders.
AQ319736045637en-000101 / DPD01798 | 125Danfoss A/S © 2021.06
Parameter List
VACON® NXP Advanced Safety Options
Operating Guide

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VACON OPTEA and is the answer not in the manual?

Danfoss VACON OPTEA Specifications

General IconGeneral
BrandDanfoss
ModelVACON OPTEA
CategoryDC Drives
LanguageEnglish

Related product manuals