Table 103: Input/Output Parameters
Input/output parameters
Value
Digital Input 1
SS1
Digital Output 2
SBC
Table 104: General Parameters
General parameters
Value
Drive Reset
Enabled
Drive Acknowledgment
Enabled 2)
Disabled 1)
Table 105: SS1 Parameters
SS1 parameters
Value
Acknowledgment Mode (SS1)
Automatic 1)
Manual 2)
SS1 Monitoring
Time
SS1 Ramp Monitoring
SS1 t1
4.75 s
SS1 td1
SS1 td2
1) and 2) indicate alternative options. Use values marked with the same number.
When you use the safety-aware Multipurpose drive application, the SS1 function is realized by the drive application when the SS1
function is requested from the Advanced safety option board. The ramp definitions for controlled ramp are taken from the ramp 2
of the drive.
Table 106: Configuration in Safety-aware Multipurpose Drive Application
Parameter
Value
P2.12.1 S Stop Response
Ramp 2
P2.4.2 Ramp 2 Shape
0
P2.4.4 Deceleration Time 2
4 s
AQ319736045637en-000101 / DPD01798 | 175Danfoss A/S © 2021.06
Configuration Examples
VACON® NXP Advanced Safety Options
Operating Guide