1-03 Torque Characteristics
Option: Function:
but if the motor power factor cos phi requires
tuning, an AMA function can be carried out
using parameter 1-29 Automatic Motor Adaptation
(AMA). It is rarely necessary to adjust the motor
power factor parameter manually.
NOTICE
Parameter 1-03 Torque Characteristics has no eect when
parameter 1-10 Motor Construction = [1] PM, non-salient
SPM.
1-04 Overload Mode
Select the torque level in overload mode.
Option: Function:
[0] High torque Allows up to 160% overtorque for
undersized motors.
[1] * Normal torque Allows up to 110% overtorque.
1-06 Clockwise Direction
Option: Function:
NOTICE
This parameter cannot be adjusted while
the motor is running.
This parameter denes the term clockwise
corresponding to the LCP direction arrow. Used for
easy change of direction of shaft rotation without
swapping motor wires.
[0] * Normal The motor shaft turns in clockwise direction when
the frequency converter is connected U⇒U, V⇒V,
and W⇒W to the motor.
[1] Inverse Motor shaft turns in counterclockwise direction
when the frequency converter is connected U⇒U,
V⇒V, and W⇒W to the motor.
3.3.2 1-1* Motor Selection
NOTICE
This parameter group cannot be adjusted while the
motor is running.
The following parameters are active depending on the
setting in parameter 1-10 Motor Construction.
Parameter 1-10 Motor
Construction
[0]
Asynchro
-
nous
[1] PM
Motor
non-
salient
[2] PM
Motor
Salient
IPM
[3]
SynRM
Motor
Parameter 1-00 Cong-
uration Mode
x x x x
Parameter 1-10 Motor
Construction
[0]
Asynchro
-
nous
[1] PM
Motor
non-
salient
[2] PM
Motor
Salient
IPM
[3]
SynRM
Motor
Parameter 1-03 Torque
Characteristics
x – - -
Parameter 1-06 Clockwi
se Direction
x x x x
Parameter 1-14 Dampi
ng Gain
– x x x
Parameter 1-15 Low
Speed Filter Time
Const.
– x x x
Parameter 1-16 High
Speed Filter Time
Const.
– x x x
Parameter 1-17 Voltage
lter time const.
– x x x
Parameter 1-20 Motor
Power [kW]
x – – –
Parameter 1-21 Motor
Power [HP]
x – – –
Parameter 1-22 Motor
Voltage
x – – –
Parameter 1-23 Motor
Frequency
x – – –
Parameter 1-24 Motor
Current
x x x x
Parameter 1-25 Motor
Nominal Speed
x x x x
Parameter 1-26 Motor
Cont. Rated Torque
– x x x
Parameter 1-28 Motor
Rotation Check
x x x x
Parameter 1-29 Autom
atic Motor Adaptation
(AMA)
x x x x
Parameter 1-30 Stator
Resistance (Rs)
x x x x
Parameter 1-31 Rotor
Resistance (Rr)
x – – –
Parameter 1-35 Main
Reactance (Xh)
x – – –
Parameter 1-37 d-axis
Inductance (Ld)
– x x x
Parameter 1-39 Motor
Poles
x x x x
Parameter 1-40 Back
EMF at 1000 RPM
– x x –
Parameter 1-44 d-axis
Inductance Sat. (LdSat)
– – – x
Parameter 1-45 q-axis
Inductance Sat. (LqSat)
– – x –
Parameter 1-46 Positio
n Detection Gain
– x x x
Parameter Description Programming Guide
MG20OB02 Danfoss A/S © 05/2018 All rights reserved. 41