Chapter 9 External Interface
PAGE 9-31
9-6-4. Fieldbus Setup
In the PROFINET I/O tab, setting of the Anybus-CompactCom PROFINET IO is performed. The network
settings, the station name, the I/O settings, and the message settings can be changed.
Default (the settings are set to the factory settings)
Network Settings
IP Address: 192.168.10.50
Subnet Mask: 255.255.255.0
Default Gateway: 192.168.10.1
Station Name: HFC3000PRT01
Setting I/O [PLC to Contorller]: 8bytes[64bits]
Setting I/O [Contorller to PLC]: 16bytes[128bits]
Message Bytes Settings [PLC to Contorller]: 32bytes
Message Bytes Settings [Contorller to PLC]: 200bytes
* Message Block Bytes is fixed at 250 bytes.
Network Settings
IP Address: 0.0.0.0 ~ 255.255.255.255
Subnet Mask: 0.0.0.0 ~ 255.255.255.255
Default Gateway: 0.0.0.0 ~ 255.255.255.255
Station Name
Setting range: ASCII characters (half-width alphanumeric characters 16 characters at max.)
Please make sure that the name is the same as the name registered at the PLC side.
If the names are not the same, network connection with the PLC side cannot be established.
Setting I/O
[PLC to Contorller]
Setting range: 2bytes[16bits] ~ 8bytes[64bits]
[Contorller to PLC]
Setting range: 2bytes[16bits] ~ 32bytes[256bits]
Message Bytes Settings
[PLC to Contorller]
Setting range: 0byte ~ 32bytes
[Contorller to PLC]
Setting range: 0byte ~ 4096bytes
S0140185-H