37 XTLtouch Series Programming Guide | Digital Monitoring Products
CROSS ZONE
Select YES to enable cross-zoning for this zone. Cross-zoning requires this zone to trip
twice, or this zone and another cross-zoned zone to trip, within a programmed time
before an alarm report is sent to the receiver.
Note: To operate correctly, all cross-zone zones need to be programmed as the same
zone type.
When a cross-zoned zone trips, the Output action assigned to the zone activates. See the
Bell Action section. The cross-zone time specified in System Options begins to count down.
See the Cross-Zone Time section. If another cross-zoned zone in the system faults, or if the
first zone restores and faults again before the cross-zone time expires, the bell turns on and
the panel sends an alarm report.
If no other cross-zoned zone in the system trips before the cross-zone time expires, the
panel sends only a fault report from the first zone to the receiver.
Note: If CRS ZONE is YES, a valid CRS ZN TIME must be programmed in System Options
for this feature to be enabled.
Cross-zoning is not compatible and cannot be enabled for Fire Verify zone types.
PRIORITY
Selecting YES allows you to provide additional protection for a zone by requiring it to be
in a normal condition before its assigned area can be armed. A priority zone cannot be
bypassed.
A Priority zone not in a normal condition cannot be armed. If a user attempts to arm
the area, the keypad displays the bad zone name followed by PRIORITY ZONE and the
arming is stopped.
TRAFFIC COUNT
This option is displayed for NT or EX type zones. Select YES to provide reporting to the
receiver of the number of zone trips while in a disarmed state. The number of trips for
each zone set as trac count are added together and included with the area closing
message and reported to the central station automation system. Default is NO.
ZONE AUDIT DAYS
Enter the number of days (0 to 99) allowed to elapse without the zone being tripped
before a fault message is sent. The message is sent to the receiver(s) programmed
to receive Supervisory/Trouble Reports at 10:00 am following the expiration of the
timer. Each time the zone is tripped, the Zone Audit Days timer restarts and begins
to countdown the number of days programmed. After the countdown expires, a fault
message is sent and the Zone Audit Days timer restarts and begins to countdown the
number of days programmed. Available for all zone types except fire and fire verify.
Enter 0 (zero) to disable this function. Default is 0 (zero).
CRS ZONE NO YES
PRIORITY NO YES
TRAFFIC COUNT
NO YES
ZONE AUDIT DAYS:
0-0