RTD Channel
(avail. signals see
Reference Manual)
URTDII Connect‐
ion Name
Terminals Temperature Monitoring Point
MB2 Group Ⅱ, RTD8 J10B-15, J10B-16 RTD Temperature of the Motor
Bearing (2)
LB1 Group Ⅲ, RTD9 J10B-12, J10B-13 RTD Temperature of the Load
Bearing (1)
LB2 Group Ⅲ, RTD10 J10B-8, J10B-9 RTD Temperature of the Load
Bearing (2)
Aux1 Group Ⅳ, RTD11 J10B-5, J10B-6 User Dened RTD Temperature.
Aux2 Group Ⅳ, RTD12 J10B-1, J10B-2 User Dened RTD Temperature.
NOTICE!
Consult the URTDII Module Instruction Leaet (I.L. IL02602013E) for complete
instructions.
Three URTD terminals are provided for each RTD input.
The three terminals for any unused RTD input channel should be wired together. For
example, if MW5 and MW6 are unused, MW5 terminals J2-15, J2-16, and J2-17 should be
wired together and MW6 terminals J2-19, J2-20, J2- 21 should be separately wired
together.
188 www.eaton.com EMR-3MP0
4 Protective Elements
4.14 URTDII Module Interface