The optical ber is the only method of transmitting temperature data from the URTDII
Module to the protective device.
Preassembled plastic optical bers with connectors can be ordered from Eaton, or from
any distributor of Agilent Technologies® optical ber products. In addition, these same
distributors oer long rolls of cable with connectors that can be installed in the eld.
Some distributors will make custom lengths to order.
NOTICE!
Force is 11 pounds (50 Newtons).
Surplus length of a pre-cut ber does not cause a problems. Simply coil and tie the excess
ber at a convenient point. Avoid high tie pressure. Bending radius of the ber should be
greater than 2 in. (50.8 mm).
The ber termination at the URTDII simply snaps into or out of the connector. To connect
the ber termination at the protective device, push the plug of the ber optic onto the
device interface then turn it until it “snaps”.
CAUTION!
The protective device as well as the URTDII have various power supply options. Make
certain that the power supply is acceptable for both units before connecting the same
power supply to both devices.
Wiring RTDs to the URTDII Module
RTD Channel
(avail. signals see
Reference Manual)
URTDII Connect‐
ion Name
Terminals Temperature Monitoring Point
WD1 Group Ⅰ, RTD1 J2-1, J2-2 RTD Temperature of the Motor
Winding 1
WD2 Group Ⅰ, RTD2 J2-5, J2-6 RTD Temperature of the Motor
Winding 2
WD3 Group Ⅰ, RTD3 J2-8, J2-9 RTD Temperature of the Motor
Winding 3
WD4 Group Ⅰ, RTD4 J2-12, J2-13 RTD Temperature of the Motor
Winding 4
WD5 Group Ⅰ, RTD5 J2-15, J2-16 RTD Temperature of the Motor
Winding 5
WD6 Group Ⅰ, RTD6 J2-19, J2-20 RTD Temperature of the Motor
Winding 6
MB1 Group Ⅱ, RTD7 J10B-19, J10B-20 RTD Temperature of the Motor
Bearing (1)
187www.eaton.comEMR-3MP0
4 Protective Elements
4.14 URTDII Module Interface