2.2.8.1.1 “TI” – Standard Phase and Ground Current Measuring Input Card
WARNING!
Ensure the correct tightening torques (see diagram).
Connection cross section:
• 1 x or 2 x 2.5 mm² (2 x AWG 14) with wire end ferrule, or:
• 1 x or 2 x 4.0 mm² (2 x AWG 12) with ring cable sleeve or cable sleeve, or:
• 1 x or 2 x 6 mm² (2 x AWG 10) with ring cable sleeve or cable sleeve.
E_F21
0.3 Nm
2.65 lb⋅in
2.0 Nm
17.7 lb⋅in
1.35 Nm
11.9 lb⋅in
Maximum Value:
Recommended:
IA-N
IA – 5A
IB-N
IC-N
IC – 5A
IX-N
IX – 5A
IB – 5A
1
2
3
4
5
6
7
8
10
11
9
12
E_F30
1
2
3
4
5
6
7
8
9
10
11
12
IA
5A
N
IB
5A
N
IC
5A
N
IX
5A
N
X3
1A
1A
1A
1A
IA – 1A
IB – 1A
IC – 1A
IX – 1A
Fig. 16: TI – Terminal Marking
82 www.eaton.com EMR-3MP0
2 Hardware
2.2 EMR-3MP0 – Installation and Wiring