5 Parameters
5.5 Digital and analog inputs
100 DC1 variable frequency drive 12/13 MN04020003Z-EN www.eaton.com
Terminal Mode (P-12 = 0)
P-15 DI1
1)
DI2
2)
DI3/AI2 AI1/DI4 Notes
0
0 = Locked
1 = Start-Enable
0 = FWD
1 = REV
0 = Selected setpoint source
1 = Fixed frequency 1 (P-20)
Setpoint value AI1
1 0 = Locked
1 = Start enable FWD
0 = Selected setpoint
source
1 = fixed frequency 1/2
0 = Fixed frequency 1 (P-20)
1 = Fixed frequency 2 (P-21)
Setpoint value AI1
2 0 = Locked
1 = Start enable FWD
DI2 DI3/AI2 DI3/AI2 Fixed
frequency
4 selectable fixed frequen-
cies:
The analog input is used as
digital input.
Switched at:
8V < V
input
< 30 V
0 0 0 FF1 (P-20) 0 = Fixed
frequency 1 - 4 (P-
20 - P-23)
1 = maximum
frequency (P-01)
1 0 0 FF2 (P-21)
0 1 1 FF3 (P-22)
1 1 1 FF4 (P-23)
3
0 = Locked
1 = Start enable FWD
0 = Selected setpoint
source
1 = fixed frequency 1
(P-20)
External fault
0 = Fault
1 = Enable
Setpoint value AI1 Used to connect an external
thermistor to DI3
4
0 = Locked
1 = Start enable FWD
0 = Analog input 1
1 = Analog input 2
Setpoint value AI2 Setpoint value AI1 Changing between analog
input: 1 and 2
5
0 = Locked
1 = Start enable FWD
0 = Locked
1 = Start enable REV
0 = Selected setpoint source
1 = Fixed frequency 1 (P-20)
Setpoint value AI1 Connection of DI1 and DI2
leads to a quick stop (P-24).
6
0 = Locked
1 = Start-Enable
0 = FWD
1 = REV
External fault
0 = Fault
1 = Enable
Setpoint value AI1 Used to connect an external
thermistor to DI3
7 0 = Locked
1 = Start enable FWD
0 = Locked
1 = Start enable REV
External fault
0 = Fault
1 = Enable
Setpoint value AI1 Connection of DI1 and DI2
leads to a quick stop (P-24).
Connection of an external
thermistor to DI3.
8
0 = Locked
1 = Start-Enable
0 = FWD
1 = REV
DI3/AI2 AI1/DI4 Fixed frequency
0 0 FF1 (P-20)
1 0 FF2 (P-21)
0 1 FF3 (P-22)
1 1 FF4 (P-23)
9
0 = Locked
1 = Start enable FWD
0 = Locked
1 = Start enable REV
DI3/AI2 AI1/DI4 Fixed frequency Connection of DI1 and DI2
leads to a quick stop (P-24).
0 0 FF1 (P-20)
1 0 FF2 (P-21)
0 1 FF3 (P-22)
1 1 FF4 (P-23)
10
1 = Run FWD
3)
0 = Stop
3)
0 = Selected setpoint source
1 = Fixed frequency 1 (P-20)
Setpoint value AI1
11 1 = Run FWD
3)
0 = Stop
3)
1 = Run REV
3)
Setpoint value AI1 Connection of DI1 and DI2
leads to a quick stop (P-24).
12
0 = Locked
1 = Start enable FWD
0 = Quick stop (P-24)
1 = Run FWD
0 = Selected setpoint source
1 = Fixed frequency 1 (P-20)
Setpoint value AI1
Note:
Negative fixed frequencies are inverted it Run REV is selected.
1) FWD switch position only for IP66 degree of protection with local controls
2) REV switch position only for IP66 degree of protection with local controls
3) Button command