11 Annex
11.19 List of parameters
DC1 variable frequency drive 12/13 MN04020003Z-EN www.eaton.com 221
11.19 List of parameters
Table 37: List of parameters
PNU
ID Access right Value Description DS Page / Appli-
cation note
RUN ro/rw
P-01 129 rw 0 - 250 Hz
(max. 500 Hz)
Maximum frequency / maximum speed 50.0 114, 114
P-02
130 rw 0 - 250 Hz
(max. 500 Hz)
Minimum frequency / minimum speed 0.0 114
P-03
131 rw 0.1-600s Acceleration time (acc1) 5.0 114; AP040016
P-04 132 rw 0.1-600s Deceleration time (dec1) 5.0 114, 107;
AP040016
P-05
133 rw Stop Function 1 118; AP040018
0 Ramp, deceleration = dynamic braking.
1 Free coasting
2 Ramp, quick stop = dynamic braking
P-06 134 rw Energy optimization 0 AP040040
0 Deactivated
1 Activated
P-07 135 rw 0.20 - 230/500 V Nominal motor voltage 230
1)
38, 114, 114;
AP040014
P-08
136 rw Depending on
device
Rated motor current 4.8
1)
38, 109;
AP040014
P-09
137 rw 25 - 500 Hz Rated motor frequency 50.0
1)
38, 114, 114;
AP040014
P-10
138 rw 0 - 30000 rpm
(min
-1)
Nominal speed of the motor 0 38, 110;
AP040022,
AP040014
P-11
139 rw 0.00 - 20.0 % Voltage amplification 3.0 114; AP040036
1) Depends on the variable frequency drive's rated power