11 Annex
11.19 List of parameters
222 DC1 variable frequency drive 12/13 MN04020003Z-EN www.eaton.com
P-12 140 rw Control level 0 98, 100, 105,
138, 153
0 Control signal terminals
1 Keypad (FWD)
2 Keypad (FWD/REV)
3 Modbus (internal ramp times)
4 Modbus (bus ramp times)
5 PI controller with external actual value
6 PI controller with external actual value and totalized
value of AI1
7 CANopen (internal ramp times)
8 CANopen (CANopen ramp times)
9 SmartWire-DT (SWD control command and setpoint
value)
10 SmartWire-DT (SWD control command; internal
setpoint value)
11 SmartWire-DT (SWD setpoint value; internal control
command)
12 SmartWire-DT (control will depend on the configura-
tion in the event of a loss of communications; auto-
matic switch to local control)
13 SmartWire-DT (SWD control command and setpoint
value; in addition, an enable signal via DI1 and an
enable setpoint via DI2)
P-13
141 ro P-dEF Fault log history 163
P-14 142 rw 0 - 9999 Access code (P-15 to P-53 101) 0 97; AP040020
Extended parameter range (access: P-14 = 101)
P-15
143 rw 0 - 12 Function of digital inputs 5 98, 100
P-16 144 rw Analog input 1 (AI1), signal range V0-10 AP040024
0 = V0-10 0 - 10-V signal (FWD)
1 = b-10-10 0 - 10-V signal (FWD/REV)
2 = AV-20 0 - 20 mA signal
3 = t4-20 4 - 20 mA signal
4 = r4-20 4 - 20 mA signal
5 = t20-4 20 - 4 mA signal
6 = r20-4 20 - 4 mA signal
P-17 145 rw 8, 12, 16, 24, 32 Pulse frequency 16
1)
1) Depends on the variable frequency drive's rated power
PNU
ID Access right Value Description DS Page / Appli-
cation note
RUN ro/rw