11 Annex
11.3 Technical data
DC1 variable frequency drive 12/13 MN04020003Z-EN www.eaton.com 173
11.3 Technical data
11.3.1 DC1-1D
Symbol
Unit
DC1-
1D2D3…
DC1-
1D4D3…
DC1-
1D5D3…
Main circuit
Rated operating voltage U
e
V 115 AC, single-phase
Mains voltage (50/60Hz) U
LN
V 110 (-10 %) - 115 (+10 %)
Input current I
LN
A 11 19 25
Mains frequency f
LN
Hz 50/60
Frequency range f
LN
Hz 48 - 62
Power section
Overload current for 60 s every 600 s I
L
A 3.45 6.45 8.7
Starting current for 2 s every 20 s I
L
A 4.03 7.53 10.15
Output voltage at U
e
U
2
V 230 AC, 3-phase
Output frequency f
2
Hz 0 - 50 (max. 500 Hz)
Pulse frequency f
PWM
kHz 16 (adjustable 4 – 32)
Frequency resolution (setpoint value) ΔfHz
0.1
Rated operational current
1)
I
e
A 2.3 4.3 5.8
Heat dissipation at rated operational
current
18.5 37.5 44
Efficiency η %
95 95 95
Maximum leakage current to earth (PE) I
PE
mA < 1 < 1 < 1
Fan, built-in
– ✓
1)
✓
1)
Size FS1 FS1 FS2
Motor feeder
Assigned motor output
at 230 V, 50 Hz P kW 0.37 0.75 1.1
at 220 - 240 V, 60 Hz P HP
0.5 1 1.5
Apparent power
Apparent power at rated operation
230 V
SkVA0.92 1.71 2.31
Apparent power at rated operation
240 V
SkVA
0.96 1.79 2.41
1) Not with IP66 degree of protection.