6 Drives control
6.2 Second acceleration and deceleration time
DC1 variable frequency drive 12/13 MN04020003Z-EN www.eaton.com 107
6.2.1 Stop function with two different deceleration times
The stop function with a deceleration time is activated with P-05 = 0
or P-05 = 2. If the enable signal on digital input DI1 (FWD, control signal
terminal 2) is switched off, the variable frequency drive's output frequency
will be reduced as required by the deceleration time (dec1) set in P-04.
The second deceleration time is set with parameter P-24.
When the device is running with its default configuration, the second
deceleration time is activated by activating DI1 and DI2 (control signal
terminals 2 and 3) simultaneously.
Figure 63: Stop function with two different deceleration times
2
DI1
DI2
3
FWD
REV
+24 V
1
+24 V Out
PNU ID Access rights Value Description DS
RUN ro/rw
P-04 132 ✓ rw 0.1 - 600 s Deceleration time (dec1) 5.0
P-24 152 ✓ rw 0.1 - 25.0 s Second deceleration time (dec2) 0.0