5 Parameters
5.5 Digital and analog inputs
102 DC1 variable frequency drive 12/13 MN04020003Z-EN www.eaton.com
SmartWire-DT (P-12 = 10)
P-15 DI1
1)
DI2
2)
DI3/AI2 AI1/DI4 Notes
0, 5,
10,
11, 12
0 = Locked
1 = Start enable FWD
Not assigned 0 = Setpoint value AI1
1 = Fixed frequency 1
Setpoint value AI1
1 0 = Locked
1 = Start enable FWD
0 = Selected setpoint
source
1 = fixed frequency 1/2
0 = Fixed frequency 1
1 = Fixed frequency 2
Setpoint value AI1
2 0 = Locked
1 = Start enable FWD
DI2 DI3/AI2 Fixed frequency 4 selectable fixed frequen-
cies:
The analog input will be used
as a digital input.
Switched if:
8V < V
input
< 30 V
0 0 FF1 (P-20) 0 = Fixed
frequency 1 - 4
(P-20 - P-23)
1 = maximum
frequency (P-01)
1 0 FF2 (P-21)
0 1 FF3 (P-22)
1 1 FF4 (P-23)
3
0 = Locked
1 = Start enable FWD
0 = Selected setpoint
source
1 = Fixed frequency 1
External fault
0 = Fault
1 = Enable
Setpoint value AI1 Used to connect an external
thermistor to DI3
4 0 = Locked
1 = Start enable FWD
0 = Setpoint value AI1
1 = setpoint value AI2
Setpoint value AI2 Setpoint value AI1 Changing between analog
input: 1 and 2
6, 7
0 = Locked
1 = Start enable FWD
Not assigned 0 = Selected setpoint source
1 = Fixed frequency 1 (P-20)
Setpoint value AI1 Connection of DI1 and DI2
leads to a quick stop (P-24).
8, 9
0 = Locked
1 = Start-Enable
0 = FWD
1 = REV
DI3 AI1 Fixed frequency 4 selectable fixed frequen-
cies:
The analog input will be used
as a digital input:
Switched if:
8V < V
input
< 30 V
0 0 FF1 (P-20)
1 0 FF2 (P-21)
0 1 FF3 (P-22)
1 1 FF4 (P-23)
Note:
Negative fixed frequencies are inverted it Run REV is selected.
1) FWD switch position only for IP66 degree of protection with local controls
2) REV switch position only for IP66 degree of protection with local controls
3) Button command