7 Applications
7.5 Motor potentiometer
128 DC1 variable frequency drive 12/13 MN04020003Z-EN www.eaton.com
Figure 80: Motor potentiometer example
If a minimum frequency has been configured (P-02), the motor potentiom-
eter will always start at f = 0 Hz. After the configured minimum frequency is
exceeded, the motor potentiometer will work within the range up to the
maximum frequency (P-01). The frequency will not fall below the minimum
frequency value unless the start enable (DI1) is switched off.
Figure 81: Motor potentiometer with f
min
limit
f
[Hz]
DI2
DI3
DI1
f
max
0 Hz
P-01
P-03 P-04
UP UP UP
DOWN
DOWN
START
f
[Hz]
DI2
DI3
DI1
f
max
0 Hz
P-01
f
min
P-02
UP UP UP
DOWN
START