7 Applications
7.6 Motor current monitoring
DC1 variable frequency drive 12/13 MN04020003Z-EN www.eaton.com 131
P-19 147 rw 0 - 200 % K1-Limit value (relay) 100.0
The adjustable limit value that is being used in connection with
settings 4 to 7 of P-18 and P-25
P-25
153 rw AO1 signal (Analog Output)
Switch to digital output
8
DO1 (digital output 1) +24 VDC (values 0 - 7)
0 RUN (variable frequency drive enabled and running – FWD, REV)
1 READY, variable frequency drive ready for operation / no faults
2 Output frequency = frequency reference value
3 Error message (variable frequency drive is not ready)
4 Output frequency limit value (P-19)
5 Output current limit value (P-19)
6 Output frequency < limit value (P-19)
7 Output current < limit value (P-19)
Analog output 0 - 10 V DC (value 8, 9)
8 Output frequency f-Out 0 - 100 % f
max
(P-01)
9 Output current 0 - 200 % I
e
(P-08)
PNU ID Access rights Value Description DS
RUN ro/rw