11 Annex
11.10 Expansion modules
DC1 variable frequency drive 12/13 MN04020003Z-EN www.eaton.com 201
11.10.2.3 Block diagram
Figure 112: Block diagram DXC-EXT-2RO
11.10.2.4 Parameter definition
The K1 relay output's function can be configured using parameter P-18.
Meanwhile, the new K2 relay output's function can be configured using
parameter P-25.
DANGER
Dangerous voltage!
Expansion module DXC-EXT-2RO must not be placed into oper-
ation until all mounting and installation work has been
completed. Any other use will be considered to be an inappro-
priate use.
→
The control signal terminals on the DC1 variable frequency drive
are plug-in terminals. They can be screwed onto the expansion
module in order to cover the pins (protection against contact).
2
DI1
3
DI2
4
DI3
1
5
+10 V
< 20 mA
6 7
0 V
8 9 10 11
1DC1 2 3 4 5 6 8 9 10 11
P-18 = 1
RUN
P-25
7
AI
0 ... +10 V
+24 V
< 100 mA
f-Soll
K2 K1
250 V AC
220 V DC
≦ 1 A
4.7 kΩ
→
For more information, please refer to application note
AP040032.
NOTICE
Parameter P-25 must be set to a value between 0 and 7 and
function as a digital output.
If it is set to a value greater than 7, the K2 relay output will not
work properly.