3.4.2 Mounting the Installation Plate to the Wall (SRC24, SRC36)
Follow this procedure and best practices when mounting the indoor unit’s plate to a wall.
1. Use the provided screws, mount the installation plate horizontally by aligning the centerline using a
leveling tool, Figure 3-11.
Figure 3-11 Installation-plate screws for SRC24 and SRC36
2. Observe the left and right rear piping clearance when drilling into the wall, Figure 3-12.
Figure 3-12 Piping clearance for SRC24 and SRC36 plate
WARNING
Risk of electrical shock. Can cause injury or death.
• When choosing a location for the wall-mount plate, be sure to take into consideration routing of
wiring for power outlets within the wall. Avoid contact with hazardous voltage wiring.
• Use caution when drilling holes through the walls for the purposes of piping connections.
Refer to 3.4.3 - Drilling a Piping Hole in the Wall, as you following the plate-installation
procedure.
NOTE
Select the location carefully. Unit should be anchored to a strong wall to
prevent unnecessary vibration.
Chassis
Hook
Type "A" Screws
Left rear piping Right rear piping
1-11/16
4-11/32
4-11/16
Unit: Inch
1-11/16
30-
11/16
13-
3/16