Safety 
Information
Introduction
Product 
Information
System 
configuration
Mechanical 
Installation
Electrical 
Installation
Getting 
Started
Basic 
parameters
Running 
the motor
Optimization
SMARTCARD 
operation
Onboard 
PLC
Advanced 
parameters
Technical 
Data
Diagnostics
UL Listing 
Information
100  Unidrive SPM User Guide
www.controltechniques.com                               Issue Number: 3
Figure 6-45 Start / stop control EN954-1 category B - replacement 
of contactor
In the second example, illustrated in Figure 6-46 and Figure 6-47, a 
conventional high-integrity system which uses two safety contactors with 
auxiliary contacts with connected movement is replaced by a single 
SAFE TORQUE OFF (SECURE DISABLE) system. This arrangement 
meets EN954-1 category 3.
Figure 6-46 Category 3 interlock using electromechanical safety 
contactors
The safety function of the example circuit is to ensure that the motor 
does not operate when the interlocks are not signalling a safe state. The 
safety relay is used to check the two interlock channels and detect faults 
in those channels. The stop/start buttons are shown for completeness as 
part of a typical arrangement, they do not carry out a safety function and 
are not necessary for the safe operation of the circuit
Figure 6-47 Category 3 interlock using SAFE TORQUE OFF 
(SECURE DISABLE) with protected wiring
In the conventional system, a contactor failure in the unsafe direction is 
detected the next time the safety relay is reset. Since the drive is not part 
of the safety system it has to be assumed that AC power is always 
available to drive the motor, so two contactors in series are required in 
order to prevent the first failure from causing an unsafe event (i.e. the 
motor driven).
With SAFE TORQUE OFF (SECURE DISABLE) there are no single 
faults in the drive which can permit the motor to be driven. Therefore it is 
not necessary to have a second channel to interrupt the power 
connection, nor a fault detection circuit.
It is important to note that a single short-circuit from the Enable input 
(STO) to a DC supply of approximately +24V would cause the drive to be 
enabled. For this reason, Figure 6-47 shows the wire from the Enable 
input to the safety relay as "protected wiring" so that the possibility of a 
short circuit from this wire to the DC supply can be excluded, as 
specified in ISO 13849-2. The wiring can be protected by placing it in a 
segregated cable duct or other enclosure, or by providing it with a 
grounded shield. The shield is provided to avoid a hazard from an 
electrical fault. It may be grounded by any convenient method, no 
special EMC precautions are required.
If the use of protected wiring is not acceptable, so that the possibility of 
this short circuit must be allowed for, then a relay must be used to 
monitor the state of the Enable input, together with a single safety 
contactor to prevent operation of the motor after a fault. This is illustrated 
in Figure 6-48.
N
The auxiliary relay K2 must be located in the same enclosure and close 
to the drive, with its coil connected as closely as possible to the drive 
enable (STO) input.
Figure 6-48 Use of contactor and relay to avoid the need for 
protected wiring
For further applications guidance, refer to the Unidrive SP Advanced 
User Guide.
Stop
Start
Drive
Enable
K1
(or at 
drive
output)
K1
+24V
~
K1
Drive
STO
M
Using contactor
Using SAFE TORQUE OFF 
(SECURE DISABLE)
T31
T31
3 ~
Stop
Start
K1
+24V
K1
Stop
Start
Drive
Enable
K1
K2
+24V
Safety
relay
Two-channel
interlocks
Reset
K1
K2
K1
K2
K1 K2
M
3 ~
STO
+24V
Safety
relay
Interlocks
Reset
(Pr )
10.02
Protected wiring
(screened or 
segregated)
SD
K1
K2
+24V
Safety
relay
Two-channel
interlocks
Reset
K1
K2
K1 K2