Safety
Information
Introduction
Product
Information
System
configuration
Mechanical
Installation
Electrical
Installation
Getting
Started
Basic
parameters
Running
the motor
Optimization
SMARTCARD
operation
Onboard
PLC
Advanced
parameters
Technical
Data
Diagnostics
UL Listing
Information
Unidrive SPM User Guide 13
Issue Number: 3 www.controltechniques.com
The continuous current ratings given are for maximum 40°C (104°F), 1000m altitude and 3.0 kHz switching. Derating is required for higher switching
frequencies, ambient temperature >40°C (104°F), high altitude and parallel applications. For further information, refer to section 14.1.1 Power and
current ratings (Derating for switching frequency and temperature) on page 263.
Table 3-1 SPMA 400V drive ratings (380V to 480V ±10%)
Table 3-2 Paralleled SPMA 400V motor drive ratings (380V to 480V ±10%)
Table 3-3 SPMA 690V drive ratings (500V to 690V ±10%)
Model
Normal Duty Heavy Duty
External 24V
current
consumption
Maximum
continuous
output
current
Peak
current
Nominal
motor
power
at 400V
Nominal
motor
power
at 460V
Maximum
continuous
output
current
Open
loop
peak
current
Closed
loop
peak
current
Nominal
motor
power
at 400V
Nominal
motor
power
at 460V
AAkW hp A AA kW hp A
SPMA14X1 205 225 110 150 180 232 270 90 150
3.3
SPMA14X2 236 259 132 200 210 271 315 110 150
Paralleled SPMA modules
Normal Duty Heavy Duty
Required
output
sharing
choke
Maximum
continuous
output
current
Peak
current
Nominal
motor
power at
400V
Nominal
motor
power at 460V
Maximum
continuous
output
current
Open
loop peak
current
Closed
loop peak
current
Nominal
motor
power
at 400V
Nominal
motor
power at 460V
AAkW hp A AAkW hp
2 x SPMA14X1
389 428 225 300 342 439 512 185 300 1 x OTL411
2 x SPMA14X2 448 493 250 400 399 513 598 225 350 1 x OTL412
3 x SPMA14X1 584 642 315 500 513 659 769 280 450 3 x OTL401
3 x SPMA14X2 672 739 355 550 598 769 897 315 500 3 x OTL402
4 x SPMA14X1 779 859 400 650 684 878 1025 355 600 4 x OTL401
4 x SPMA14X2 896 986 500 750 798 1026 1197 400 700 4 x OTL402
5 x SPMA14X1 973 1071 550 850 855 1098 1281 450 750 5 x OTL401
5 x SPMA14X2 1121 1233 600 950 997 1282 1496 550 850 5 x OTL402
6 x SPMA14X1 1168 1285 650 1000 1026 1318 1538 550 900 6 x OTL401
6 x SPMA14X2 1345 1479 750 1150 1197 1539 1795 650 1050 6 x OTL402
When connecting drives in parallel they must be derated. Table 3-2, Table 3-4, Table 3-6, Table 3-8 and Table 3-10 have already the
required de-rating.
NOTE
Model
Normal Duty Heavy Duty
External 24V
current
consumption
Maximum
continuous
output
current
Peak
current
Nominal
motor
power
at 690V
Nominal
motor
power
at 575V
Maximum
continuous
output
current
Open
loop
peak
current
Closed
loop
peak
current
Nominal
motor
power
at 690V
Nominal
motor
power
at 575V
AAkW hp A AA kW hp A
SPMA16X1
125 137 110 125 100 128 149 90 100
3.3
SPMA16X2
144 158 132 150 125 160 187 110 125

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Unidrive SPM and is the answer not in the manual?

Emerson Unidrive SPM Specifications

General IconGeneral
BrandEmerson
ModelUnidrive SPM
CategoryController
LanguageEnglish

Related product manuals