Safety 
Information
Introduction
Product 
Information
System 
configuration
Mechanical 
Installation
Electrical 
Installation
Getting 
Started
Basic 
parameters
Running 
the motor
Optimization
SMARTCARD 
operation
Onboard 
PLC
Advanced 
parameters
Technical 
Data
Diagnostics
UL Listing 
Information
Unidrive SPM User Guide      115
Issue Number: 3                      www.controltechniques.com
Use Pr 0.05 to select the required frequency/speed reference as follows:
Setting Pr 0.05 to 1, 2 or 3 will re-configure T28 and T29. Refer to 
Pr 8.39 (Pr 0.16 in OL) to disable this function.
Pr 0.06 limits the maximum output current of the drive (and hence 
maximum motor torque) to protect the drive and motor from overload.
Set Pr 0.06 at the required maximum torque as a percentage of the rated 
torque of the motor, as follows:
(%)
Where:
T
R 
Required maximum torque
T
RATED
 Motor rated torque
Alternatively, set 0.06 at the required maximum active (torque-
producing) current as a percentage of the rated active current of the 
motor, as follows:
(%)
Where:
I
R 
Required maximum active current
I
RATED
  Motor rated active current
8.2.4     Voltage boost, (open-loop), Speed-loop PID 
gains (closed-loop) 
Open-loop
There are six voltage modes available, which fall into two categories, 
vector control and fixed boost. For further details, refer to section  Pr 
0.07 {5.14} Voltage mode on page 137.
Software V01.10.00 and later, the defaults are as above.
Software V01.09.01 and earlier, the default is 0.0100 in Closed-loop 
vector and servo mode.
Closed-loop
Pr 0.07 (3.10) operates in the feed-forward path of the speed-control 
loop in the drive. See Figure 13-4 on page 174 for a schematic of the 
speed controller. For information on setting up the speed controller 
gains, refer to Chapter 10 Optimization on page 136.
Open-loop
When 0.07 Voltage mode selector is set at Fd or SrE, set Pr 0.08 (5.15) 
at the required value for the motor to run reliably at low speeds. 
Excessive values of Pr 0.08 can cause the motor to be overheated.
Software V01.10.00 and later, the defaults are as above.
Software V01.09.01 and earlier, the default is 1.00 in Closed-loop vector 
and servo modes.
Closed-loop
Pr 0.08 (3.11) operates in the feed-forward path of the speed-control 
loop in the drive. See Figure 13-4 on page 174 for a schematic of the 
speed controller. For information on setting up the speed controller 
gains, refer to Chapter 10 Optimization on page 136.
Open-loop
Set Pr 0.09 (5.13) at 0 when the V/f characteristic applied to the motor is 
to be fixed. It is then based on the rated voltage and frequency of the 
motor.
Set Pr 0.09 at 1 when reduced power dissipation is required in the motor 
when it is lightly loaded. The V/f characteristic is then variable resulting 
in the motor voltage being proportionally reduced for lower motor 
currents. Figure 8-2 shows the change in V/f slope when the motor 
current is reduced.
 
0.05 {1.14} Reference selector
RW Txt NC US
Ú
0 to 5
Ö
A1.A2 (0)
Setting
A1.A2 0
Analog input 1 OR analog input 2 selectable by digital 
input, terminal 28
A1.Pr 1
Analog input 1 OR preset frequency/speed selectable 
by digital input, terminal 28 and 29
A2.Pr 2
Analog input 2 OR preset frequency/speed selectable 
by digital input, terminal 28 and 29
Pr 3 Pre-set frequency/speed
PAd 4 Keypad reference
Prc 5 Precision reference
0.06 {4.07} Current Limit
RW Uni RA US
Ú
0 to Current_limit_max %
Ö
OL 138.1
VT 165.7
SV 150.0
0.07 {5.14} Voltage mode selector
RW Txt US
OL
Ú
Ur_S (0), Ur (1), Fd (2), 
Ur_Auto (3), Ur_I (4), 
SrE (5)
Ö
Ur_I (4)
0.06[]
T
R
T
RATED
--------------------
100×=
0.06[]
I
R
I
RATED
-------------------
100×=
0.07 {3.10} Speed controller proportional gain
RW Uni US
CL
Ú
0.0000 to 6.5535
1/rad s
-1
Ö
VT 0.0300
SV 0.0100
0.08 {5.15} Low frequency voltage boost
RW Uni US
OL
Ú
0.0 to 25.0% of motor 
rated voltage
Ö
1.0
0.08 {3.11} Speed controller integral gain
RW Uni US
CL
Ú
0.00 to 655.35
1/rad
Ö
VT 0.10
SV 1.00
0.09 {5.13} Dynamic V/F / flux optimize select
RW Bit US
OL
Ú
OFF (0) or On (1)
Ö
OFF (0)