8.3 Solving Problems Not Indicated by Status Messages
Situation Description Recommended Actions
Digital Outputs Not Working
Properly (cont.)
Outputs on extension board(s)
(XDIO) affected
XDIO: If LED "TIMEOUT"
glows - c
heck jumpers on
XDIO.
XDIO #1: jumper on ADR2
XDIO #2: jumpers on ADR2
& ADR0
XDIO: If LED "TIMEOUT"
glows - check connection to
P33
XDIO: If LED "NO SPI" glows
- check internal SPI commu-
nication cable (10 pole cable)
Digital Inputs Not Working
Properly
External failure
Check external circuitry for
failures
Conguration failure
Check digital inputs menu
settings
Outputs on extension board(s)
(XDIO) affected
XDIO: If LED "TIMEOUT"
glows - c
heck jumpers on
XDIO.
XDIO #1: jumper on ADR2
XDIO #2: jumpers on ADR2
& ADR0
XDIO: If LED "TIMEOUT"
glows - check connection to
P33
XDIO: If LED "NO SPI" glows
- check internal SPI commu-
nication cable (10 pole cable)
Internal Valves Not Working
Properly
Connection failure
Check electrical connection
of valves
XPSA: If red LED "TI-
MEOUT" glows - check con-
nection to P33
XPSA: LED "TIMEOUT" dark
- check power connection to
XPSA (2-pole cable br/wht)