5Operation PROline Promag 53
82 Endress+Hauser
5.4.5 Switching HART write protection on and off
A jumper on the I/O board provides the means of activating or deactivating HART write
protection.
#
Warning:
Risk of electric shock. Exposed components carry dangerous voltages. Make sure
that the power supply is switched off before you remove the cover of the electronics
compartment.
Wait at least 10 minutes for heat to dissipate before opening an Ex-rated device.
1. Switch off power supply.
2. Remove the I/O board Page 112, 114
3. Switch HART write protection on or off, as applicable, by means of the jumper
(Fig. 46).
4. Installation of the I/O board is the reverse of the removal procedure.
Fig. 46: Switching HART write protection on and off
1 HART write protection OFF (default), that is: HART protocol unlocked.
2 HART write protection ON , that is: HART protocol locked.
F06-x3xxxxxx-16-xx-06-xx-000