5Operation PROline Promag 53
70 Endress+Hauser
5.4.2 Device and process variables
Device variables:
The following device variables are available using the HART protocol:
Process variables:
At the factory, the process variables are assigned to the following device variables:
Primary process variable (PV) Volume flow
Second process variable (SV) Totalizer 1
Third process variable (TV) Mass flow
Fourth process variable (FV) not assigned
!
Note!
You can set or change the assignment of device variables to process variables using
Command 51 (see Page 76).
5.4.3 Universal / Common practice HART commands
The following table contains all the universal and common practice commands sup-
ported by Promag 53.
Code (decimal) Device variable
0 OFF (not assigned)
1 Volume flow
2Mass flow
250 Totalizer 1
251 Totalizer 2
252 Totalizer 3
Command No.
HART command / Access type
Command data
(numeric data in decimal form)
Response data
(numeric data in decimal form)
Universal Commands
0 Read unique device identifier
Access type = read
none Device identification delivers information on the
device and the manufacturer. It cannot be
changed.
The response consists of a 12 byte device ID:
Byte 0: fixed value 254
Byte 1: Manufacturer ID, 17 = E+H
Byte 2: Device type ID, 66 = Promag 53
Byte 3: Number of preambles
Byte 4: Universal commands rev. no.
Byte 5: Device-specific commands rev. no.
Byte 6: Software revision
Byte 7: Hardware revision
Byte 8: Additional device information
Bytes 9-11: Device identification