Proline Promass 83 PROFIBUS DP/PA Trouble-shooting
Endress+Hauser 127
359
...
362
S: PULSE RANGE
!: # 359...362
0x54
0x55
0x56
UNCERTAIN Engineering
Unit Range
Violation
O.K.
Low
High
Flow is Out of
Range
Cause:
Pulse output: Pulse output frequency is out of range.
Remedy:
1. Increase the setting for pulse weighting
2. When selecting the pulse width, choose a value
that can still be processed by a connected
counter (e.g. mechanical counter, PLC etc.).
Determine the pulse width:
– Variant 1: Enter the minimum duration that
a pulse must be present at the connected
counter to ensure its registration.
– Variant 2: Enter the maximum (pulse)
frequency as the half “reciprocal value” that
a pulse must be present at the connected
counter to ensure its registration.
Example:
The maximum input frequency of the
connected counter is 10 Hz. The pulse width to
be entered is:
F06-83xxxxxx-19-xx-xx-xx-006
3. Reduce flow.
379 S LOW FREQ. LIM
$ # 379
0x0F BAD Device Failure Constant Frequence limit 1 Cause:
The measuring tube oscillation frequency is outside
the permitted range.
Causes:
Measuring tube damaged
Sensor defective or damaged
Remedy:
Contact your E+H service organisation.
380 S UPPER FREQ. LIM
$ # 380
0x0F BAD Device Failure Constant Frequence limit 2 Cause:
The measuring tube oscillation frequency is outside
the permitted range.
Causes:
Measuring tube damaged
Sensor defective or damaged
Remedy:
Contact your E+H service organisation.
381 S FLUIDTEMP.MIN.
$ # 381
0x10
0x11
0x12
BAD Sensor Failure O.K.
Low
High
Fluid
Temperature
Min.
Cause:
The temperature sensor on the measuring tube is
likely defective.
Remedy:
Check the following electrical connections before
you contact your E+H service organisation:
• Verify that the sensor signal cable connector is
correctly plugged into the amplifier board
→ Page 139 ff.
• Remote version: Check sensor and transmitter
terminal connections No. 9 and 10
→ Page 30 ff.
No. Device status message
(local display)
PROFIBUS measured value status
Adv. diagnosis
message in
PROFIBUS
master
Cause/remedy
Quality code (HEX)
Quality status
Quality substatus
Limits
ms
Hz
50
102
1