Proline Promass 83 PROFIBUS DP/PA Commissioning
Endress+Hauser 83
7. Select the operating mode (GSD file) which should be used for cyclic communication with the
PROFIBUS master.
BASIC FUNCTION (G) → PROFIBUS DP (GBA) → OPERATION (614)
→ SELECTION GSD (6140) → Select:
– MANUFACT. SPEC. (factory setting): Promass 83 measuring device is operated in the
manufacturer-specific mode.
– MANUFACT V2.0: Promass 83 is used as the replacement for the previous Promass 63
model (compatibility mode).
– GSD PROFILE: Promass 83 is operated in the Profile mode.
!
Note!
For PROFIBUS network configuration, make sure that the right GSD file of the measuring
device is used for the selected operating mode:
!
Note!
Further information on the device master file → Page 86
8. Configuration of cyclic data transmission in the PROFIBUS master: a detailed description of the
system integration can be found on → Page 86
Operating mode Device master file (GSD file)
MANUFACT. SPEC. “eh3x1529.GSD” or “eh3_1529.GSD” (depends on the PROFIBUS master used)
MANUFACT V2.0 “eh3x1512.GSD” or “eh3_1512.GSD” (depends on the PROFIBUS master used)
GSD PROFILE “PA039742.GSD”