Commissioning Proline Promass 83 PROFIBUS DP/PA
82 Endress+Hauser
6. Configuration of totalizers 1-3:
Promass 83 has 3 totalizers. The following example describes the configuration of totalizer 1.
• In the “CHANNEL” parameter, select the measured variable (e.g. mass flow) to be
transmitted to the PROFIBUS master as the totalizer value 1:
BASIC FUNCTION (G) → PROFIBUS DP (GBA) → TOTALIZER (613)...
... → SELECT TOTALIZER (6130) → Select: TOTALIZER 1
... → CHANNEL (6133) → Select: MASS FLOW
or enter the ID by means of the operating program: 277
Possible settings: see following table.
• Enter the desired totalizer units:
BASIC FUNCTION (G) → PROFIBUS DP/PA (GBA) → TOTALIZER (613)
→ UNIT TOTALIZER (6134)
• Configure totalizer status, e.g. totalise:
BASIC FUNCTION (G) → PROFIBUS DP/PA (GBA) → TOTALIZER (613)
→ SET TOTALIZER (6135) → Select: TOTALISE
• Set the totalizer mode, e.g. for balancing:
BASIC FUNCTION (G) → PROFIBUS DP/PA (GBA) → TOTALIZER (613)
→ TOTALIZER MODE (6137) → Select: BALANCE
The following settings are possible:
Batch counter 1348
Total batching quantity 1349
Batching time 1354
The following measured variables are available when the additional “advanced diagnostics” software is installed (order
option)
Mass flow deviation 1603
Density deviation 1620
Reference density deviation 1637
Temperature deviation 1654
Tube damping deviation 1671
Actual deviation electr. dyn. sensors 1688
Measured variable ID for “CHANNEL” parameter
Mass flow (factory setting totalizers 1...3) 277
Volume flow 273
Corrected volume flow 398
The following measured variables are available when the additional “concentration measurement” software is installed
(order option)
Target mass flow 1164
Target volume flow 1167
Corrected target volume flow 1169
Carrier mass flow 1170
Carrier volume flow 1172
Corrected carrier volume flow 1174
Measured variable ID for “CHANNEL” parameter