Proline Promass 83 PROFIBUS DP/PA Commissioning
Endress+Hauser 91
Assignment of the measured variables to the AI module
The AI module can transmit different measured variables to the PROFIBUS master system.
The measured variables are assigned to the Analog Input function blocks 1…6 by means of the local
display or with the aid of a class 2 master (operating program) in the “CHANNEL” parameter:
Configuration via the local display:
Function group BASIC FUNCTION PROFIBUS DP FUNCTION BLOCKS BLOCK
SELECTION CHANNEL
Configuration via the operating program:
Analog Input function block 1…6 CHANNEL parameter
Factory setting:
The following settings are possible:
Module Analog Input function
block
Measured variable factory
setting
“CHANNEL” parameter
factory setting
AI (slot 1) 1 Mass flow 277
AI (slot 2) 2 Volume flow 273
AI (slot 3) 3 Corrected volume flow 398
AI (slot 4) 4 Density 281
AI (slot 5) 5 Reference density 402
AI (slot 6) 6 Temperature 285
Measured variable ID for “CHANNEL” parameter
Mass flow 277 (factory setting AI 1)
Volume flow 273 (factory setting AI 2)
Corrected volume flow 398 (factory setting AI 3)
Density 281 (factory setting AI 4)
Reference density 402 (factory setting AI 5)
Temperature 285 (factory setting AI 6)
The following measured variables are available when the additional “concentration measurement” software is installed
(order option)
Target mass flow 1164
% target mass flow 1165
Target volume flow 1167
% target volume flow 1168
Corrected target volume flow 1169
Carrier mass flow 1170
% carrier mass flow 1171
Carrier volume flow 1172
% carrier volume flow 1173
Corrected carrier volume flow 1174
% Black liquor 1166