01-ECMSI-NT002.Rev B40
Multipoint detectors ref: MISTRA 50 & 100
BUS
H2 H1 L2 L1
FIRE FAULT
BALTIC 512 TYPE A WALL OR RACK BOX CONTROL AND SIGNALING EQUIPMENT 512 POINTS
28
1 detector per line max. of the
line (1000m)
Entrance 1
Entrance 2
Entrance 3
0V
EARTH
24V
Entrance 4
All of the "Mistral 50" and/
or "Mistral 100" connected
to a single FI-AT must not
monitor an area of more
than 1600m²
CNS
B
AT
Entrance 5
Entrance 6
Entry 7
Ra
Entry 8
EAE/AES+
24V
RFL
(NFS 61940)-
(EN 54-4)
bindings Cable to be used for connecting the linear detector
230VAC
AES<->Mistral
Section(min.)
Kind
2x1.5mm²
CR1 (Fire Resistant)
brown
black
orange
gold
brown
black
red
gold
Section(min.)
Kind
1 pair - 8/10th without screen
C2 (non-propagator)
RFL = 10 kOhms 1/2W RA= 1 kOhm 1/2W
FIAT<->Mistral