01-ECMSI-NT002.Rev B40
Wiring AMP1 spoken message sirens
of the exit
diffusers
sound
of the CMSI
-UGA
+ UGA
- DS
+ DS
7 sirens max. per line (external AES mandatory)
Features
electric
AMP1 sirens
Cable to be used for connecting the sirens
Voltage: 10 to 58Vdc
Cons. : 130mA (24Vdc)
140mA (48Vdc)
RFL = 10 kOhms - 1/4W
Section(min.)
Kind
2 x 1.5mm² min.
CR1(fire resistant)
Wiring of AMP2 synchro spoken message sirens
AMP2 siren AMP2 siren AMP2 siren "EIP" interface
of the exit
diffusers
sound
of the CMSI
EXIT ENTRANCE
+ - + -
7 sirens max. per line (external AES mandatory)
Features
electric
AMP2 sirens
Cable to be used for connecting the sirens
Voltage: 10 to 58Vdc
Cons. : 130mA (24Vdc)
140mA (48Vdc)
RFL = 10 kOhms
1/4W
Section(min.)
Kind
2 x 1.5mm² min.
CR1(fire resistant)
BALTIC 512 TYPE A WALL OR RACK BOX CONTROL AND SIGNALING EQUIPMENT 512 POINTS
56
InteIrnfatecrefa"cEeIP""EIP"
-UGA
- UGA
+ UGA
+ UGA
- DS
- DS
+ DS
+ DS
ModMuoledudleedyencsh
yn
rocnhirsoantiion
station
- +
- +
-
-
+
+
- +
- +
- +
- +
-
-
+
+
- +
- +