01-
ECMSI-NT002.Rev B40
Interview
→ The operator is required to keep his installation in good working order;
→ maintenance
must be carried out by a technician attached to the establishment or a qualified professional.
→ in
accordance with the regulations*, the installation must be covered by a maintenance contract.
Periodic
checks
→ Daily
verification operations
- Test of the panel's audible and visual signaling
by pressing the "signalling test" and
"report" keys.
-
observation of the state of the AES;
- ECS examination.
→ Monthly
verification operation
• Unlocking
test of emergency exit unlocking devices
→ Quarterly
verification operations
• Testing
of DAS for fire safety functions such as sound diffusers, fire doors,
smoke extraction motor…. ) as well as technical stops (eg non stop lift) from a detection point.
→ Half-
yearly verification operations
• Test
from a detection point of CMSI functions
→ Annual verification operations
- Functional
test of each automatic detector and each manual call point;
-
testing of dampers and shutters;
- testing
of control devices;
- visual
inspection of each DAS (including those with position control and remote
reset);
- functional
test of the alarm equipment (broadcasting of the emergency evacuation sound signal).
Battery maintenance
→ The
system automatically monitors battery charge and status, including internal impedance.
→ Battery
replacement
The
batteries must be replaced every 4 years or before this period in the event of a persistent battery fault indication.
* Article MS58 of the safety regulations against the
risk of fire and panic in establishments open to the public.
†
It is essential to respect the type and capacity of the original batteries.
CONTROL AND SIGNALING EQUIPMENT 512 POINTS BALTIC 512 TYPE A WALL OR RACK BOX