order to limit the broadcast of the emergency evacuation sound signal, the other tests may be carried out in "restricted"
standby mode.
Test
of the general evacuation manual control
For
this test, the ECS and the UGA/CMSI must be in “standby” mode. Only the green "power on" light is on. The
goal :check
the activation of the sound diffusers following a manual control at the level of the panel.
Stock Report If the signage
is different...
→ Three successive
beeps sound;
→ the
buzzer emits a continuous sound;
1.
Press and hold the "general
evacuation control" button
→ the red “general evacuation”
light
comes on steady
→ Check the wiring of the sound
diffusers
→ the
sound diffusers emit the
signal; general evacuation for
5 min.
→ The red "general
evacuation" light goes out;
2.
After the general evacuation
→ the
sound diffusers stop.
Testing
the fire protection functions
For
this test, the ECS and the UGA/CMSI must be in “standby” mode.
Only
the green “power on” indicator light is on.
The
goal :check the activation of the safety functions and the operation of the DAS.
Stock Report If the signage
is different...
1.
Press the "manual control" key of
the tripping function to be tested.
→ The
red “safety” indicator light for the
activated function lights up steadily;
→ Look for
the reason using the
table description of the
signals
→ the board buzzer
emits a continuous
sound
2.
Reset the board
Ö
→ The red "safety"
light
goes out;
Type
the level 2 code
(BBBB by default)
Ö press
"reset".
→ the
red “alarm” light goes out.
I
Do not forget to reset the activated DAS.
BALTIC
512 TYPE A WALL OR RACK BOX CONTROL AND SIGNALING EQUIPMENT 512 POINTS