01-ECMSI-NT002.Rev B40
Wiring of Axendis 10110LST conventional sirens
Electrical characteristics of
conventional sirens
Cable to be used for wiring conventional sirens
1 CR1 type cable, 2 conductors 1.5mm² to 2.5mm² (fire retardant)
Voltage: 15 to 60 VDC;
consumption : 12.2 to 29.4mA
RFL (end of line resistance: optional (in case of line monitoring), 10KΩ s
Number of 10110LST conventional sirens per line
E/IP interface I/I2P interface
Internal AES External AES External AES External AES
12V 24V 48V 24V 48V
Quantity
/ 32 32 32 32
Wiring of Axendis 10130 recorded message sirens
Electrical characteristics of
10130 recorded message sirens
Cable to be used for wiring 10130 recorded message sirens
Voltage: 10 to 60 Vdc
Conso. : 80 to 375mA
1 CR1 type cable, 2 conductors 1.5mm² to 2.5mm² (fire retardant)
RFL (end of line resistance: optional (in case of line monitoring), 10KΩ s
Number of recorded message sirens 10130 per line
E/IP interface I/I2P interface
Internal AES External AES External AES External AES
12V 24V 48V 24V 48V
Quantity
/ 2 2 5 5
BALTIC 512 TYPE A WALL OR RACK BOX CONTROL AND SIGNALING EQUIPMENT 512 POINTS