INTRODUCTION 7
Message Problem
Switching 1
Switching power supply 1 Fault
Mains fault The Control panel is NOT powered from the Mains
Battery The Control panel batteries charger not working properly
Low battery The Control panel batteries are empty
Earth Leakage to Earth
24A Output 24A Output is shorted
24R Output 24R Output is shorted
Flash writing Flash writing error
Flash erasing LOG erasing error
Main controller Main controller fault
Firmware main contr. Checksum fault
Prog.data main cont Data programming Checksum fault
Prog.data tel.board Aux Controller data programming Checksum fault
Loop Communication Communication Loop fault controller
Not programmed dev Loop device without address
Loop return open Loop negative signal open
Loop signal open Loop positive signal open
Loop local short Local short on Loop controller
Loop right short Right side Loop short
Loop left short Left side Loop short
Non answer Loop device doesn' t answer
Dirty level (Smoke detector ONLY) the dirty threshold has been exceeded
Short circuit Short circuit on Input module
Open circuit Open circuit on Input module
Power supply Main fault
Wrong value A Loop device has a wrong value
Stuck output An Output module relay is not switched
Same address Several Loop devices have the same address
Wrong Type Different loop device from that programmed in the panel
IP Communicator The communication with IP controller is lost
IP receiver The communication with IP receiver is lost
Display communic. Communication fault on Display controller
PSTN communicator The communication with PSTN controller is lost
Telephone line Telephone Line fault
LOG Full LOG fault
Backup PSTN line Backup Telephone Line fault
PSTN Action not Ack. A PSTN action has not been acknowledged
SC x short SC x= (1 or 2) short circuit
SC X open SC x (1 or 2) open terminal
Transistor SC x Transistor SC x (1 or 2) fault
Table 1 Faults table (Continued..)