E018-P
FLOWRATE MONITOR / TOTALIZER
with linearization, high / low alarms, analog and pulse signal
outputs and HART communication
Signal input: Flowmeter - type P: Pulse, NAMUR and coil
Signal outputs: Analog referenced flowrate
Scaled or unscaled pulse referenced total
Remote control: External reset with clear-lock
Options: HART communication
E-Series - Explosion proof indicators for hazardous areas
More info: www.fluidwell.com/eseries

Table of Contents

Other manuals for Fluidwell E018

Questions and Answers

  • R
    Rodney MillerSep 12, 2025
    Why does the Fluidwell E018 Measuring Instruments flowrate display "0 / zero" while there is flow (total is counting)?
    • J
      John MartinSep 12, 2025
      If the Fluidwell Measuring Instruments flowrate displays "0 / zero" while the total is counting, the issue might be: * Incorrect K-factor and time unit. * A mismatch between the flowrate calculation setting and the flowrate cut-off. For example, if the cut-off is set to 10.0 seconds, the unit needs at least 10 seconds to measure the number of pulses according to the calculation.
  • E
    Eileen JohnsonSep 14, 2025
    What to do if the pulse output of my Fluidwell E018 Measuring Instruments does not function?
    • M
      Michael HernandezSep 14, 2025
      If the pulse output of your Fluidwell Measuring Instruments isn't functioning, verify: * The function mode. * The pulse per quantity. * The pulse width compatibility with the external device.