80 Upgrade and Maintenance Manual BX900 S2
Basic software procedures
© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: C:\Programme\FCT\tim_app\tim_local\work\WALTER\OBJ_DOKU-13655-001.fm
5.2.9 Verifying power consumption
I This task applies only, if a PSU must be replaced, which has not failed
completely.
Ê Login to the management blade web interface, see section "Accessing the
management blade web interface" on page 44.
Ê Open the Information/Operation Operation Power Management menu,
select the Configuration tab and scroll to the Power Consumption Options box.
If a redundancy mode is selected in the Redundancy pull down (for
example 3+1) you can replace the PSU with no problems.
If No Redundancy is selected in the Redundancy pull down and if the
Remaining Output Power is less than ca. 3200 W, you must shut down
some server blades before replacing the PSU.
I The Remaining Output Power value is displayed in the status frame
of the management blade web interface.