EasyManua.ls Logo

GE 269Plus

GE 269Plus
218 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
A-
2
269Plus Motor Management Relay GE Power Management
EXAMPLE A 269 PLUS UNBALANCE EXAMPLE
A
Therefore, the unbalance is
When a motor is lightly loaded however, the ratio of negative sequence to positive sequence current will
increase as the positive sequence current becomes a relatively small value. This may result in nuisance trips
even though a lightly loaded motor can withstand relatively large amounts of unbalance. The 269Plus derates
unbalance below Full Load by multiplying the unbalance by .
Assuming full load = 100% of CT, the 15.34% unbalance now becomes:
Finally, the ratio of negative sequence to positive sequence current for any magnitude of phase current may be
displayed on a graph as shown below (providing the supply is a true three phase supply and there is no zero
sequence current flowing, no ground fault).
Figure A–3: NEGATIVE TO POSITIVE SEQUENCE CURRENT RATIO
I
n
I
p
----
I
2
I
1
----
1
3
---
I
a
x
2
I
b
xI
c
++()
1
3
---
I
a
xI
b
x
2
I
c
++()
-------------------------------------------
where
x
1120° 0.5 j0.866+== = =
3.9 0° 1 120°
2
5 112.95° 1120°5 112.95°++
3.9 0° 1 120°5 112.95° 1120°
2
5 112.95°++
-------------------------------------------------------------------------------------------------------------------------------------------
=
3.9 0° 5 127.05° 5 232.95°++
3.9 0° 57.05° 5352.95°++
-------------------------------------------------------------------------------------------=
3.9 3.01 j3.99 3.01 j3.99+
3.9 4.96 j0.61 4.96 j0.61++ +
----------------------------------------------------------------------------------=
2.12
13.82
---------------
= –0.1534=
0.1534 100%× 15.34%=
I
avg
I
FLC
3.955++()
1.0 5×
--------------------------------
15.34%× 14.22%=

Table of Contents

Related product manuals