FVP 110 Fieldbus Valve Positioner Manual
186
GE Energy
23 1023 NV_CYCLE_
T
0 Cycle of saving the settings of non-volatile
attribute parameters to the EEPROM. 0 is set
with the FVP110, and saving is not cyclically
done.
24 1024 FREE_
SPACE
0 Shows the free space memory for
configurations as a percent value. FVP110
shows zero which means the pre-configured
resource.
25 1025 FREE_TIME 0 Shows the free time that can be used for
computations by resources but not supported
by the FVP110.
26 1026 SHED_RCAS 640000 Communication time-out setting for
communications with the device from which the
remote cascade setpoint is sent.
27 1027 SHED_ROUT 640000 Communication time-out setting for
communications with the device from which the
remote output setting is sent; not used in the
FVP110, however.
28 1028 FAULT_
STATE
1 Indicates the fault-state.
29 1029 SET_FSTATE 1 Sets the fault-state.
30 1030 CLR_FSTATE 1 Clears the fault-state.
31 1031 MAX_NOTIFY 3 Maximum number of alerts retained in the
device (FVP110).
32 1032 LIM_NOTIFY 3 Maximum number of alerts to be held by the
device (YVP110); used by the user to restrict
the number of alert notifications to the host to
prevent overflow of alert receptions in the host.
33 1033 CONFIRM_
TIM
20000 (ms) Defines the time to wait for confirmation for an
alert.
34 1034 WRITE_
LOCK
Unlocked Prohibits write access from outside the device
to the settings.
35 1035 UPDATE_
EVT
Shows the contents of an update event upon
occurrence.
36 1036 BLOCK_ALM Shows the contents of an alarm event upon
occurrence.
Table 60 Resource Block Parameters (Continued)
Relative
Index
Index Parameter
Name
Default
(factory
setting)
Write Description