Hydran* M2-X Instruction Manual
MA-029 Rev. 1.0, 30-Jul-18
Description
a
Priority
Alarm Set Point
c
Fault Trigger
d
Low-Low sensor temperature
High
Alarm Lo-Lo SP
S. Temp L-Low Alr
Low sensor temperature
Alarm Low SP
S. Temp Low Alarm
High sensor temperature
b
Alarm Hi SP
S. Temp Hi Alarm
High-High sensor
temperature
b
Alarm Hi-Hi SP
S. Temp Hi-Hi Alarm
Table 6-5: Hydran Sensor Temperature Alarm Conditions
a. All conditions likely indicate a faulty heating system.
b. The High and High-High alarms could be caused by a very high oil temperature.
c. Found in Alarms > Alarms Setup > Temp. Alarm Setup > Sensor Temp. Alarm
d. Found in Alarms > Alarms Setup > Sys. Fault Trigger
6.3.2.2 Base Plate Temperature Alarm Conditions
The parameters pertaining to these alarm conditions are presented in Table 6-6
6-6 below. The heater plate temperature is measured using two thermistors in the
heater plate.
Description
a
Priority
Alarm Set Point
c
Fault Trigger
d
Low-Low base plate
temperature
High
Alarm Lo-Lo SP
B.P. Temp L-Low Alr
Low base plate temperature
Alarm Low SP
B.P. Temp Low Alarm
High base plate temperature
b
Alarm Hi SP
B.P. Temp Hi Alarm
High-High base plate
temperature
b
Alarm Hi-Hi SP
B.P. Temp Hi-Hi
Alarm
Table 6-6: Base Plate Temperature Alarm Conditions
a. All conditions likely indicate a faulty heating system.
b. The High and High-High alarms could be caused by a very high oil temperature.
c. Found in Alarms > Alarms Setup > Temp. Alarm Setup > Heater Plate Temp. Alarm
d. Found in Alarms > Alarms Setup > Sys. Fault Trigger
6.3.2.3 Battery Voltage Alarm Conditions
The parameters pertaining to the alarm conditions are presented in Table 6-7
below.