Hydran* M2-X Instruction Manual
MA-029 Rev. 1.0, 30-Jul-18
Low-Low sensor temperature
High-High sensor
temperature
b
Table 6-5: Hydran Sensor Temperature Alarm Conditions
a. All conditions likely indicate a faulty heating system.
b. The High and High-High alarms could be caused by a very high oil temperature.
c. Found in Alarms > Alarms Setup > Temp. Alarm Setup > Sensor Temp. Alarm
d. Found in Alarms > Alarms Setup > Sys. Fault Trigger
6.3.2.2 Base Plate Temperature Alarm Conditions
The parameters pertaining to these alarm conditions are presented in Table 6-6
6-6 below. The heater plate temperature is measured using two thermistors in the
heater plate.
Low-Low base plate
temperature
Low base plate temperature
High base plate temperature
b
High-High base plate
temperature
b
Table 6-6: Base Plate Temperature Alarm Conditions
a. All conditions likely indicate a faulty heating system.
b. The High and High-High alarms could be caused by a very high oil temperature.
c. Found in Alarms > Alarms Setup > Temp. Alarm Setup > Heater Plate Temp. Alarm
d. Found in Alarms > Alarms Setup > Sys. Fault Trigger
6.3.2.3 Battery Voltage Alarm Conditions
The parameters pertaining to the alarm conditions are presented in Table 6-7
below.